YASKAWA TM.iQp.07 iQpump Controller Programming Manual
Parameter List
Table 123 Parameter List
Parameter
No.
Addr.
Hex
Parameter Name
Digital Operator
Display
Description
Setting
Range
Factory
Setting
Menu
Location
Page
No.
Initialization
A1-00
0100
Language Selection
Select Language
Language selection for digital operator display.
0: English
2: Deutsch
3: Francais
4: Italiano
5: Espanol
6: Portugues
*Not returned to factory setting by initialization
0 ~ 6
0
Programming
A1-01
0101
Access Level Selection
Access Level
This setting determines which parameters are accessible.
0: Operation Only
2: Advanced Level
0 or 2
2
Programming
A1-03
0103
Initialize Parameters
Init Parameters
Used to return all parameters to their factory or user setting.
0: No Initialize
1110: User Initialize (The user must set their own parameter default
values and then parameter o2-03 must be set to “1” to save them. If the
parameter values are changed after o2-03 is set to “1”, the user default
values can be restored by setting A1-03 to 1110.)
2220: 2-Wire Initial
3330: 3-Wire Initial
0 ~ 3330
0
Programming
A1-04
0104
Password 1
Enter Password
When the value set into A1-04 does NOT match the value set into A1-
05, parameters A1-01 thru A1-03 cannot be changed. All other
parameters as determined by A1-01 can be changed. Parameter A1-05
can be accessed by pressing the MENU key while holding the RESET
key.
0 ~ 9999
0
Programming
A1-05
0105
Password 2
Select Password
0 ~ 9999
0
Programming
Denotes that parameter can be changed when the drive is running. * Menu location is Pump Quick Setup when b5-01=1, and Programming when b5-01=0.
Sequence
b1-01
0180
Frequency Reference
Selection
Reference Source
Selects the speed command (frequency reference) input source.
0: Operator - Digital preset speed d1-01
1: Terminals - Analog Input Terminal A1 (or Terminal A2 see
parameter H3-13)
2: Serial Com - RS-485 Terminals R+, R-, S+ and S-
3: Option PCB - Option board connected at 2CN
0 ~ 3
0
Programming
b1-02
0181
Run Command Selection
Run Source
Selects the run command input source.
0: Operator - “Hand” and “Off” keys on digital operator
1: Terminals - Contact Closure on Terminal S1
2: Serial Com - RS-485 Terminals R+, R-, S+ and S-
3: Option PCB - Option board connected at 2CN
5: Timed Run
<0034>
0 ~ 3, 5
0
Programming
b1-03
0182
Stopping Method
Selection
Stopping Method
Selects the stopping method when the run command is removed.
0: Ramp to Stop
1: Coast to Stop
2: DC Injection to Stop
3: Coast w / Timer (A new run command is ignored if input before the
time in C1-02 expires.)
0 ~ 3
0
Programming
b1-07
0186
Local / Remote Run
Selection
LOC/REM RUN Sel
0: Cycle External RUN - If the run command is closed when switching
from hand (local) mode to auto (remote) mode, the drive will not run.
1: Accept External RUN - If the run command is closed when
switching from hand (local) mode to auto (remote) mode, the drive
WILL run.
Note:
Used with LCD Operator only.
0 ~ 1
0
Programming
—
b1-08
0187
Run Command Selection
During Program
RUN CMD at PRG
0: Disabled - Run command accepted only in the operation menu.
1: Enabled - Run command accepted in all menus (except when
b1-02 = 0).
0 ~ 1
0
Programming
—
b1-11
010F
Drive Delay Time Setting
Wait to Run Time
After a run command, drive output will start after this delay time.
0 ~ 600 s
0 s
Programming
DC Braking
b2-01
0189
DC Injection Braking
Start Frequency
DCInj Start Freq
Sets the frequency at which DC injection braking starts when ramp to
stop (b1-03 = 0) is selected. If b2-01 < E1-09, DC injection braking
starts at E1-09.
0.0 ~
10.0 Hz
0.5 Hz
Programming