BPS / MX / RS Series SCPI Programming Manual

AMETEK Programmable Power

Manual P/N 7003-961 Rev. AA

65

MEASure:CURRent:HARMonic:PHASe?

[3Pi Controller Only]

FETCh:CURRent:HARMonic:PHASe?

[3Pi Controller Only]

Phase Selectable

These queries return the phase angle of the Nth harmonic of output current, referenced to
the positive zero crossing of the fundamental component.

The parameter is the desired harmonic number. Queries sent with a value of 0 return the dc
component. A value of 1 returns the fundamental output frequency. Harmonic orders can be
queried up to the fundamental measurement bandwidth of the measurement system:

MX Series I:

25.6 microseconds for single-phase mode and 76.8 microseconds for three-

phase mode.

MX/RS Series II: 10.4 microseconds for single-phase mode and 31.2 microseconds for
three-phase mode.

Thus the maximum harmonic that can be measured is dependent on the output frequency.
Any harmonics that represent frequencies greater than above frequencies are returned as 0.

Query Syntax

MEASure[:SCALar]:CURRent:HARMonic:PHASe?

FETCh[:SCALar]:CURRent:HARMonic:PHASe?
Parameters

0 to 50

Examples MEAS:CURR:HARM:PHAS? 3 FETC:CURR:HARM:PHAS? 1
Returned Parameters

Related Commands

INST:NSEL

MEASure:CURRent:HARMonic:THD? ]

[3Pi Controller Only]

FETCh:CURRent:HARMonic:THD?

[3Pi Controller Only]

Phase Selectable

These queries return the percentage of total harmonic distortion and noise in the output
current.

Query Syntax

MEASure[:SCALar]:CURRent:HARMonic:THD?

FETCh[:SCALar]:CURRent:HARMonic:THD?
Parameters None
Examples MEAS:CURR:HARM:THD? FETC:CURR:HARM:THD?
Returned Parameters

Related Commands

INST:NSEL