Manual P/N 7003-961 Rev AA

8.3.2

Interharmonics Subsystem

The following commands are used to enable and generate an interharmonic waveform up to
20% of the programmed voltage value.

[:SOURce]
:IHARmonics

[:STATe]

Enable or disable the interharmonics generator.

:COUPle

Couple the interharmonics reference to program

volt.
:FREQuency

Set

the

interharmonics

frequency.

:REFerence

Set

the

interharmonics

reference.

:VOLTage

Set the interharmonics output as % of reference.

[:SOURce]:IHARmonics[:STATe]

This command enables the interharmonics generator. This command must be set to the on
state before sending any other command listed in this section.

Command Syntax

[:SOURce]:IHARmonics:STATe

Parameters

Examples IHAR

ON

Query Syntax

IHAR?

Returned Parameters

[:SOURce]:IHARmonics:COUPle

If this command is turned on, the reference voltage for the interharmonics is programmed to
a value equal to the ac program value. If the coupling is turned off, the reference voltage
must be programmed to a value between 0 and 250V.

Command Syntax

[:SOURce]:IHARmonics:COUPle

Parameters

Examples IHAR:COUP

ON

Query Syntax

IHAR:COUP?

Returned Parameters

[:SOURce]:IHARmonics:FREQuency

This command will program the inter harmonic frequency. This frequency may range from
1Hz to 2400Hz with 1Hz resolution.

Command Syntax

[:SOURce]:IHARmonics:FREQuency

Parameters

Examples IHAR:FREQ

400

Query Syntax

IHAR:FREQ?

Returned Parameters