EVCO EPU2LXP1CH Installer manual User Manual
Page 94

EVCO S.p.A.
c-pro 3 micro CHIL | Application manual ver. 1.0 | Codice 144CP3CHE104
page 94 of 120
AC02
Operating hours compressor #2
Auto
Display only
AC03
Operating hours compressor #3
Auto
Display only
AC04
Operating hours compressor #4
Auto
Display only
AC05
Operating hours compressor #5
Auto
Display only
AC06
Operating hours compressor #6
Auto
Display only
AP01
Operating hours pump #1
Auto
Display only
AP02
Operating hours pump #2
Auto
Display only
AP03
Operating hours source pump #1
Auto
Display only
AP04
Operating hours source pump #2
Auto
Display only
AF01
Operating hours fan Circuit #1
Auto
Display only
AF02
Operating hours fan Circuit #2
Auto
Display only
AL06
Source flow meter
A/M
Compressors OFF
Pump ON for
T-secs.
Settable delay
In manual stop, pump OFF
AL83
Source anti-frost Circuit #1
Manu
Circuit compressors OFF and
Pump ON for T-secs.
AL84
Source anti-frost Circuit #2
Manu
Circuit compressors OFF and
Pump ON for T-secs.
ERTC
RTC Alarm broken or discharged
A/M
Inhibits management of RTC
-
EN01
Expansion communication alarm
Auto
Display only
Settable delay
EVM1
EVCM Circuit #1 communication alarm
Auto
All circuit compressors OFF
Settable delay
EVM2
EVCM Circuit #2 communication alarm
Auto
All circuit compressors OFF
Settable delay
ES01
External ambient temperature probe
Auto
Inhibits functions using it
ES02
System input temperature probe (FC)
Auto
Inhibits functions using it
ES03
Remote aux. temperature probe aux
(accumulation tank)
Auto
Inhibits functions using it
ES04
Heat sink exchanger input temperature probe
Auto
Settable number of ON
compressors
Settable delay
ES05
Circuit 1 heat sink exchanger output temperature
probe
Auto
Settable number of ON
compressors
ES06
Circuit 1 heat source exchanger output
temperature probe
Auto
Inhibits functions using it
ES07
Circuit 1coil temperature probe
Auto
Inhibits functions using it
ES08
Circuit 1 condenser pressure probe
Auto
Settable fan forcing
ES09
Circuit 1 evaporation pressure probe
Auto
Settable fan forcing
ES10
Circuit 1 single pressure probe
Auto
Settable fan forcing
ES11
Circuit 1 compressor discharge temperature
probe
Auto
Inhibits functions using it
ES12
Circuit 1 compressor intake temperature probe
Auto
Inhibits functions using it
ES13
Circuit 2 heat sink exchanger output temperature
probe
Auto
Settable number of ON
compressors
ES14
Circuit 2 heat source exchanger output
temperature probe
Auto
Inhibits functions using it
ES15
Circuit 2 coil temperature probe
Auto
Inhibits functions using it
ES16
Circuit 2 condenser probe
Auto
Settable fan forcing
ES17
Circuit 2 evaporation probe
Auto
Settable fan forcing
ES18
Circuit 2 single pressure probe
Auto
Settable fan forcing
ES19
Circuit 2 compressor discharge temperature
probe
Auto
Inhibits functions using it
ES20
Circuit 2 compressor intake temperature probe
Auto
Inhibits functions using it
AHW1
Duplicate configuration of analog input
Auto
Display only
AHW2
Duplicate configuration of digital input
Auto
Display only
AF03
Operating hours fan free-cooling
Auto
Display only