EVCO EPU2LXP1CH Installer manual User Manual
Page 110

EVCO S.p.A.
c-pro 3 micro CHIL | Application manual ver. 1.0 | Codice 144CP3CHE104
page 110 of 120
meForTempAlarm
0x0707
1800
PA09_DifferentialAla
rmTemp
0.5
0.1
18.0
PA09 - Differential alarm high/low temperature
R/W
0x0708
1801
PA10_DelayAfterUni
tOn
15
0
999
PA10 - Delay temperature alarm after unit on
R/W
0x0709
1802
PA11_SetAlarmLow
Press
3.0
0.1
143.5
PA11 - Setpoint alarm low pressure
R/W
0x070A
1803
PA12_DiffAlarmLow
Press
1.0
0.1
58.0
PA12 - Differential alarm Low Pressure
R/W
0x070B
1804
PA13_TimeByPassAl
armLowPress
120
0
999
PA13 - Delay alarm low pressure
R/W
0x070C
1805
PA14_NumEvHourL
P
3
0
5
PA14 - Number of alarms for manual restore type
R/W
0x070D
1806
PA16_EnabLPcontro
lLowTemp
1
0
1
PA16 - Enable low pressure alarm at startUp with low
temperature
R/W
0x070E
1807
PA17_SetAlarmLPwi
thLT
1.0
0.1
143.5
PA17 - Setpoint alarm low pressure with low
temperature
R/W
0x070F
1808
PA18_DiffAlarmLow
PressWithLowTemp
0.5
0.1
58.0
PA18 - Differential Alarm Low Pressure With Low
Temperature
R/W
0x0710
1809
PA19_TimeActiveCo
ntrolLPwithLT
120
10
999
PA19 - Time activation control low pressure with low
temperature
R/W
0x0711
1810
PA20_DelayAlarmLP
atStartUpCmp
240
0
999
PA20 - Delay alarm low pressure at startUp first
compressor
R/W
0x0712
1811
PA21_SetHPal
28.0
0.0
652.5
PA21 - Setpoint high pressure alarm
R/W
0x0713
1812
PA22_DiffHPal
5.0
0.1
435.0
PA22 - Differential for reset high pressure alarm
R/W
0x0714
1813
PA25_EnAllPrimaryE
xchanger
0
0
1
PA25 - Enable primary exchanger efficiency alarm
R/W
0x0715
1814
PA26_MinDiffPrimar
yExchanger
2.0
0.1
36.0
PA26 - Min difference threshold for primary
exchanger
R/W
0x0716
1815
PA27_ByPassAllPrim
aryExchanger
120
0
999
PA27 - By-pass timer for primary exchanger
efficiency alarm
R/W
0x0717
1816
PA30_EnableAlarmR
TC
1
0
1
PA30 - Enable alarm RTC
R/W
0x0718
1817
PA31_ResetType_Al
armRTC
1
0
1
PA31 - Reset Type Alarm RTC
R/W
0x0719
1818
PA32_ThermalFanF
C_Delay
10
0
999
R/W
0x071A
1819
PA33_ThermalFanF
CResetType
1
0
1
R/W
0x071B
1820
PA40_En_Alarm_Ho
urCmp
1
0
1
PA40 - Enable alarm of operating hours of
compressors
R/W
0x071C
1821
PA41_ThermalCmp_
Delay
10
0
999
PA41 - Delay of compressors thermal alarm
R/W
0x071D
1822
PA42_ThermalCmp_
ResetType
1
0
1
PA42 - Type of reset for compressors thermal alarm
R/W
0x071E
1823
PA50_Enable_Sourc
eFlowAlarm
0
0
1
R/W
0x071F
1824
PA51_SourceFlowSt
artup_AlarmDelay
10
1
999
R/W
0x0720
1825
PA52_SourceFlowRu
nning_AlarmDelay
1
1
999
R/W
0x0721
1826
PA53_MinFlowWater
Valve
5.00
0.00
100.00
R/W