meForTempAlarm

0x0707

1800

PA09_DifferentialAla
rmTemp

0.5

0.1

18.0

PA09 - Differential alarm high/low temperature

R/W

0x0708

1801

PA10_DelayAfterUni
tOn

15

0

999

PA10 - Delay temperature alarm after unit on

R/W

0x0709

1802

PA11_SetAlarmLow
Press

3.0

0.1

143.5

PA11 - Setpoint alarm low pressure

R/W

0x070A

1803

PA12_DiffAlarmLow
Press

1.0

0.1

58.0

PA12 - Differential alarm Low Pressure

R/W

0x070B

1804

PA13_TimeByPassAl
armLowPress

120

0

999

PA13 - Delay alarm low pressure

R/W

0x070C

1805

PA14_NumEvHourL
P

3

0

5

PA14 - Number of alarms for manual restore type

R/W

0x070D

1806

PA16_EnabLPcontro
lLowTemp

1

0

1

PA16 - Enable low pressure alarm at startUp with low
temperature

R/W

0x070E

1807

PA17_SetAlarmLPwi
thLT

1.0

0.1

143.5

PA17 - Setpoint alarm low pressure with low
temperature

R/W

0x070F

1808

PA18_DiffAlarmLow
PressWithLowTemp

0.5

0.1

58.0

PA18 - Differential Alarm Low Pressure With Low
Temperature

R/W

0x0710

1809

PA19_TimeActiveCo
ntrolLPwithLT

120

10

999

PA19 - Time activation control low pressure with low
temperature

R/W

0x0711

1810

PA20_DelayAlarmLP
atStartUpCmp

240

0

999

PA20 - Delay alarm low pressure at startUp first
compressor

R/W

0x0712

1811

PA21_SetHPal

28.0

0.0

652.5

PA21 - Setpoint high pressure alarm

R/W

0x0713

1812

PA22_DiffHPal

5.0

0.1

435.0

PA22 - Differential for reset high pressure alarm

R/W

0x0714

1813

PA25_EnAllPrimaryE
xchanger

0

0

1

PA25 - Enable primary exchanger efficiency alarm

R/W

0x0715

1814

PA26_MinDiffPrimar
yExchanger

2.0

0.1

36.0

PA26 - Min difference threshold for primary
exchanger

R/W

0x0716

1815

PA27_ByPassAllPrim
aryExchanger

120

0

999

PA27 - By-pass timer for primary exchanger
efficiency alarm

R/W

0x0717

1816

PA30_EnableAlarmR
TC

1

0

1

PA30 - Enable alarm RTC

R/W

0x0718

1817

PA31_ResetType_Al
armRTC

1

0

1

PA31 - Reset Type Alarm RTC

R/W

0x0719

1818

PA32_ThermalFanF
C_Delay

10

0

999

R/W

0x071A

1819

PA33_ThermalFanF
CResetType

1

0

1

R/W

0x071B

1820

PA40_En_Alarm_Ho
urCmp

1

0

1

PA40 - Enable alarm of operating hours of
compressors

R/W

0x071C

1821

PA41_ThermalCmp_
Delay

10

0

999

PA41 - Delay of compressors thermal alarm

R/W

0x071D

1822

PA42_ThermalCmp_
ResetType

1

0

1

PA42 - Type of reset for compressors thermal alarm

R/W

0x071E

1823

PA50_Enable_Sourc
eFlowAlarm

0

0

1

R/W

0x071F

1824

PA51_SourceFlowSt
artup_AlarmDelay

10

1

999

R/W

0x0720

1825

PA52_SourceFlowRu
nning_AlarmDelay

1

1

999

R/W

0x0721

1826

PA53_MinFlowWater
Valve

5.00

0.00

100.00

R/W