EVCO EPU2LXP1CH Installer manual User Manual

Page 34

background image

EVCO S.p.A.

c-pro 3 micro CHIL | Application manual ver. 1.0 | Codice 144CP3CHE104

page 34 of 120

PA89

Setpoint for the high temperature

discharge gas alarm of circuit 2

90.0

70.0

140.0

°C

IS-S

PA90

Differential for the high temperature

discharge gas alarm of circuit 2

20.0

10.0

30.0

°C

IS-S

PA99

Notification delay interval for

expansion alarm

5

0

999

Sec.

IS-S

MODBUS PARAMETERS

PH11

Card Modbus address

1

1

247

IS-M

PH12

Card communication baud rate

(1=2400, 2=4800, 3=9600,

4=19200)

3

1

4

IS-M

PH13

Modbus parity (0=none, 1=Odd,

2=Even)

2

0

2

IS-M

PH14

Modbus stop bit (0=1 bit, 1=2 bits)

0

0

1

IS-M

VARIOUS PARAMETERS

PH01

It sets the minimum full-scale value

for the low pressure sensor.

0.0

-10.0

PH02

Bar

IS-V

PH02

It sets the maximum full-scale value

for the low pressure sensor.

20.0

PH01

60.0

Bar

IS-V

PH03

It sets the minimum full-scale value

for the high pressure sensor.

0.0

-10.0

PH04

Bar

IS-V

PH04

It sets the maximum full-scale value

for the high pressure sensor.

50.0

PH03

45.0

Bar

IS-V

PH05

It enables the start-up/shutdown of

the machine by pressing the

ESC/Stand-By key.

Yes (1)

No (0)

Yes (1)

IS-V

PH06

It enables the change of

summer/winter operating mode:

automatic change-over.

No (0)

No (0)

Yes (1)

IS-V

PH07

It enables the start-up/shutdown of

the machine from a digital input.

No (0)

No (0)

Yes (1)

IS-V

PH08

It enables the change of

summer/winter operating mode from

digital input.

No (0)

No (0)

Yes (1)

IS-V

PH09

It enables the start-up/shutdown of

the machine by supervisor.

No (0)

No (0)

Yes (1)

IS-V

PH10

It enables the change of

summer/winter operating mode via

supervisor.

No (0)

No (0)

Yes (1)

IS-V

PH15

It resets the factory-set parameter

defaults.

No (0)

No (0)

Yes (1)

IS-V

Wait for the 0

value to be

re-read at the

end of

resetting.

PH16

It enables the start-up/shutdown of

the machine by the schedule

No (0)

No (0)

Yes (1)

IS-V

PH27

It sets the enabling of the dynamic

set point function.

No (0)

No (0)

Yes (1)

IS-V

PH28

It sets the enabling of the secondary

set point function by scheduler.

No (0)

No (0)

Yes (1)

IS-V

PH30

Cancel alarm history

NO (0)

NO (0)

YES (1)

-

IS-V

Set SI (1) and

wait for value

NO (0)

PH31

It sets the type of refrigerant used

5

0

6

IS-V