EVCO EPU2LXP1CH Installer manual User Manual
Page 28

EVCO S.p.A.
c-pro 3 micro CHIL | Application manual ver. 1.0 | Codice 144CP3CHE104
page 28 of 120
PC46
Pressure set point for high-
temperature pressure-switch control
27.0
0.0
45.0
Bar
IS-R
PC47
Pressure differential for high-
temperature pressure-switch control
2.0
0.0
5.0
Bar
IS-R
PC48
External high temperature threshold
for pressure-switch control
12.0
-30.0
23.0
°C
IS-R
PC49
Min. time for maintaining pressure-
switch partialization
10
0
99
Min.
IS-R
PC50
Enabling of low-temperature
pressure-switch control (heat pump)
No (0)
No (0)
Yes (1)
IS-R
PC51
Pressure setpoint for low-temperature
pressure-switch control
3.2
0.0
10.0
Bar
IS-R
PC52
Pressure differential for low-
temperature pressure-switch control
2.0
0.0
10.0
Bar
IS-R
PC53
External low temperature threshold
for pressure-switch control
-5.0
-10.0
5.0
°C
IS-R
PC54
Outlet water high-temperature
threshold for pressure-switch control
48.0
30.0
70.0
°C
IS-R
PC55
Delay for partialization from low
pressure alarm
900
0
999
Sec.
IS-R
PC61
Summer commutation set point
20.0
PC62
70.0
°C
IS-R
PC62
Winter commutation set point
10.0
0.0
PC61
°C
IS-R
PC64
Max. dynamic offset compared to
summer set point (chiller)
-10.0
-20.0
20.0
°C
IS-R
PC65
Compensation start temperature for
dynamic summer set point
30.0
-15.0
PC66
°C
IS-R
PC66
Compensation stop temperature for
dynamic summer set point
60.0
PC65
70.0
°C
IS-R
PC67
Max. dynamic offset compared to
winter set point (heat pump)
10.0
-20.0
20.0
°C
IS-R
PC68
Compensation start temperature for
dynamic winter set point
0.0
-15.0
PC69
°C
IS-R
PC69
Compensation stop temperature for
dynamic winter set point
30.0
PC68
70.0
°C
IS-R
PC70
Function limit management:
0 = Heat pump only
1 = Auxiliary output
2 = Auxiliary output and heat pump
0
0
2
IS-R
PC71
Function limit set point
-7.0
-30.0
30.0
°C
IS-R
PC72
Function limit differential
4.0
0.1
10.0
°C
IS-R
PC80
Enabling of control upon request
No (0)
No (0)
Sì (1)
IS-R
PC81
Summer setpoint controlupon request
15.0
-15.0
70.0
°C
IS-R
PC82
Winter setpoint control upon request
45.0
-15.0
70.0
°C
IS-R
PC83
Summer differential control upon
request
4.0
0.1
10.0
°C
IS-R
PC84
Winter differential control upon request
4.0
0.1
10.0
°C
IS-R
PC85
Delayed control upon request
5
0
999
Sec
IS-R
FANS
PF01
Condenser control type
0
0
1
IS-F
0=Modulating
control
1=Single
stage control
PF02
It gives the choice to enable fan
Yes (1)
No (0)
Yes (1)
IS-F