EVCO EPU2LXP1CH Installer manual User Manual

Page 23

background image

EVCO S.p.A.

c-pro 3 micro CHIL | Application manual ver. 1.0 | Codice 144CP3CHE104

page 23 of 120

day1

2= working

day2

PT25

Friday schedule

1

0

2

OR

0= none

working day

1= working

day1

2= working

day2

PT26

Saturday schedule

0

0

2

OR

0= none

working day

1= working

day1

2= working

day2

PT27

Sunday schedule

0

0

2

OR

0= none

working day

1= working

day1

2= working

day2

Level

1

USER MENU

ModE

It sets the operating mode:

0: Cool, (Chiller/summer)

1: Heat (Heat pump/winter)

0

0

1

UT

Modifiable

only if the

units is a

chiller + heat

pump:

(PG00=2,4)

SPC1

It sets the value of the summer set

point (chiller)

8.5

PC21

PC22

°C

UT

SPH1

It sets the value of the winter set

point (heat pump).

44.0

PC23

PC24

°C

UT

PUC1

Offset for the summer set point by

digital input

2.0

-20.0

20.0

°C

UT

PUH1

Offset for the winter set point by

digital input

-2.0

-20.0

20.0

°C

UT

PSd1

It modifies the password at User

level.

0

-999

9999

UT

Level

2

MAINTENANCE MENU

OPERATION

PM00

It sets the maximum number of

operating hours of compressors.

When this limit is exceeded, the

connected alarm is triggered.

2000

0

9999

Hrs. x10

MA-F

PM01

PM02

PM03

PM04

PM05

PM06

It shows the number of operating

hours of compressors. One parameter

for each compressor.

0

0

9999

Hrs.

x10

MA-F

PM30

It sets the maximum number of

operating hours of pumps. When this

2000

0

9999

Hrs. x10

MA-F