c-pro 3 micro CHIL | Application manual ver. 1.0 | Codice 144CP3CHE104

page 27 of 120

compressor.

PC07

Min. time which must elapse between

start-ups of two different

compressors.

360

0

999

Sec.

IS-C

PC08

Min. time which must elapse between

shutdowns of two different

compressors.

180

0

999

Sec.

IS-C

PC09

Max. number of start-ups for every

hour (only for adaptive control).

8

4

12

IS-C

PC10

Number of compressors per circuit

which will be forced in case of a

regulating-sensor alarm.

1

0

PG03

IS-C

REGULATION

PC11

It sets the control type for

compressor management:

0: Lateral band

1: Zero energy band

1

0

1

IS-R

PC12

Proportional band for lateral-band

control of compressors

2.5

1.0

20.0

°C

IS-R

PC14

Zone value for neutral-zone control of

compressors

3.0

PC15

PC16

°C

IS-R

PC15

Min. value of compressor zero energy

band

1.0

0.1

10.0

°C

IS-R

PC16

Max. value of compressor zero energy

band

5.0

0.1

10.0

°C

IS-R

PC17

Enabling/release time for subsequent

compressor step outside the zero

energy band

20

0

999

Sec.

IS-R

PC18

Enabling for auto-adaptive control of

the compressors’ zero energy band

No (0)

No (0)

Yes (1)

IS-R

PC21

Min. value of summer set point

(chiller)

5.0

-15.0

SPC1

°C

IS-R

PC22

Max. value of summer set point

(chiller)

20.0

SPC1

23.0

°C

IS-R

PC23

Min. value of winter set point

(heat pump)

30.0

23.0

SPH1

°C

IS-R

PC24

Max. value of winter set point

(heat pump)

44.0

SPH1

70.0

°C

IS-R

PC31

Power limiting for summer

50

0

100

%

IS-R

PC32

Power limiting for winter

50

0

100

%

IS-R

PC35

Enabling of forced shutdown of

compressors

No (0)

No (0)

Yes (1)

IS-R

PC36

Summer forced shutdown set point

3.5

-30.0

23.0

°C

IS-R

PC37

Winter forced shutdown set point

52.0

26.0

75.0

°C

IS-R

PC41

Enabling of pump-down

0 : No

1 : Yes, with timing

2 : Yes, with relative threshold

1

0

2

IS-R

PC42

Compressor shutdown time in pump-

down

5

0

240

Sec.

IS-R

PC43

Relative threshold for pump-down

disabling

1.5

0.0

5.0

Bar

IS-R

PC45

Enabling of high-temperature

pressure-switch control (chiller)

No (0)

No (0)

Yes (1)

IS-R