c-pro 3 micro CHIL | Application manual ver. 1.0 | Codice 144CP3CHE104

page 33 of 120

with the compressor thermal alarm

PA42

It sets the type of reset for the

compressor thermal alarm

0: A - Automatic

1: M – Manual

M

A (0)

M (1)

IS-S

PA50

Enable Source Flow alarm

No (0)

No (0)

Yes (1)

IS-S

Only for

Water-Water

unit

PA51

Source Flow alarm delay from

machine start-up

10

1

999

Sec.

IS-S

Only for

Water-Water

unit

PA52

Source Flow alarm by-pass time

during normal operation

1

1

999

Sec.

IS-S

Only for

Water-Water

unit

PA53

Minimum water valve opening to test

the flow of the heat source exchanger

5.0%

0.0%

100.0%

%

IS-S

Only for

Water-Water

unit

PA60

It enables the alarm connected with

operating hours of pumps

Yes (1)

No (0)

Yes (1)

IS-S

PA61

It enables the alarm connected with

operating hours of source pumps

No (0)

No (0)

Yes (1)

IS-S

Only for

Water-Water

unit

PA62

It sets the type of reset for the water

pump thermal alarm

0: Auto - Automatic

1: Manu - Manual

M

A (0)

M (1)

IS-S

PA63

It sets the type of reset for the source

water pump thermal alarm

0: Auto - Automatic

1: Manu - Manual

M

A (0)

M (1)

IS-S

Only for

Water-Water

unit

PA71

It sets the type of reset of high

pressure alarm restoration

0: Auto - Automatic

1: Manu - Manual

M

A (0)

M (1)

IS-S

PA80

It enables the alarm connected with

operating hours of condensing fans

Yes (1)

No (0)

Yes (1)

IS-S

PA81

It sets the triggering delay connected

with the condensing fan thermal

alarm

10

0

999

Sec.

IS-S

PA82

It sets the type of reset for the

condensing fan thermal alarm

0: A - Automatic

1: M – Manual

M

A (0)

M (1)

IS-S

PA85

Setpoint for the high temperature

discharge gas alarm of circuit 1

90.0

70.0

140.0

°C

IS-S

PA86

Differential for the high temperature

discharge gas alarm of circuit 1

20.0

10.0

30.0

°C

IS-S

PA87

It sets the triggering delay connected

with the high temperature discharge

gas

30

0

999

Sec.

IS-S

PA88

It sets the type of reset for the high

temperature discharge gas

0: A - Automatic

1: M – Manual

M

A (0)

M (1)

IS-S