EVCO EPU2LXP1CH Installer manual User Manual
Page 109

EVCO S.p.A.
c-pro 3 micro CHIL | Application manual ver. 1.0 | Codice 144CP3CHE104
page 109 of 120
0x06EB
1772
Pr06_DiffAlarmAntif
reeze
2.0
0.1
18.0
Pr06 - Differential alarm antifreeze
R/W
0x06EC
1773
Pr11_EnableAntiFre
ezeHeater_Src
0
0
1
Pr11 - Enable antifreeze heater
R/W
0x06ED
1774
Pr12_SetpointHeate
r_Src
5.0
-30.0
50.0
Pr12 - Setpoint heater
R/W
0x06EE
1775
Pr13_DiffHeater_Sr
c
2.0
0.1
18.0
Pr13 - Differential heater
R/W
0x06EF
1776
Pr14_ForceHeaterEr
rorProbe_Src
0
0
1
Pr14 - Forcing of anti-frost heating elements when
sensor error
R/W
0x06F0
1777
Pr15_SetpointAlarm
Antifreeze_Src
3.0
-30.0
50.0
Pr15 - Setpoint alarm antifreeze
R/W
0x06F1
1778
Pr16_DiffAlarmAntif
reeze_Src
2.0
0.1
18.0
Pr16 - Differential alarm antifreeze
R/W
0x06F2
1779
PS01_Enable_FreeC
ooling
0
0
1
R/W
0x06F3
1780
PS02_DiffModulatio
n_FC
3.0
0.1
20.0
R/W
0x06F4
1781
PS03_MinSpeed_FC
0.00
0.00
100.00
R/W
0x06F5
1782
PS04_MaxSpeed_FC
100.
00
0.00
100.00
R/W
0x06F6
1783
PS05_Eanbel_FreeC
ooling_WithComp
1
0
1
R/W
0x06F7
1784
PS06_SetDiffEnable
_FC
3.0
0.5
10.0
R/W
0x06F8
1785
PS07_Diff_FC
2.0
0.5
5.0
R/W
0x06F9
1786
PS08_DiffValveOnOf
f_FC
0.5
0.1
5.0
R/W
0x06FA
1787
PS09_DiffValveAO_
FC
2.0
0.1
20.0
R/W
0x06FB
1788
PS10_MinTimeForFr
eeCooling
30
0
240
R/W
0x06FC
1789
PS15_Enable_FC_P
artCond
1
0
1
R/W
0x06FD
1790
PS16_SetPartCond_
FC
11.0
0.5
20.0
R/W
0x06FE
1791
PS17_DiffPartCond_
FC
3.0
0.1
10.0
R/W
0x06FF
1792
PA01_FlowStartup_
AlarmDelay
10
1
999
PA01 - Delay alarm flow from startUp
R/W
0x0700
1793
PA02_FlowRunning_
AlarmDelay
1
1
999
PA02 - Delay Flow Running Alarm
R/W
0x0701
1794
PA03_NumberFlowA
larmaToManual
3
0
9
PA03 - Number flow alarm to became manual
R/W
0x0702
1795
PA04_DelayErrorPro
be
10
0
240
PA04 - Delay error sensor
R/W
0x0703
1796
PA05_SetpointAlar
mHighTemp
30.0
10.0
104.0
PA05 - Setpoint alarm high temperature
R/W
0x0704
1797
PA06_SetpointAlar
mLowTemp
15.0
10.0
104.0
PA06 - Setpoint alarm low temperature
R/W
0x0705
1798
PA07_DelayTempAl
arm
30
1
999
PA07 - Delay for temperature alarm
R/W
0x0706
1799
PA08_consequentTi
0
0
1
PA08 - Enable Temperature Alarm
R/W