8.19

Miscellaneous Management

8.19.1

Set point variation by schedule timer

Via parameter PH28 it is possible to adjust the setpoint by the schedule timer (set relative parameters of scheduler). Actual control

setpoint depends by the working day and relative offset.

8.19.2

Dynamic set point

Via parameter Dynamic set point enable PH27, it is possible to perform compensation of the dynamic set point on outdoor air

temperature. In this case, the control set point will take on a value between the standard set point (equivalent to the External-

temperature initial threshold) and the set point plus a Dynamic offset (equivalent to the External-temperature final threshold), both for

chiller and heat pump operation. Between the two compensation points, movement is linear, and the curve takes on a different

meaning, according to the offset sign.

With offsets of less than zero value, behavior is as follows:

The parameters referred to this function are the following:

PC64 = Maximum dynamic offset for summer operation (chiller)

PC65 = Compensation start temperature for dynamic summer set point

PC66 = Compensation stop temperature for dynamic summer set point.

With offsets greater than zero, behavior is as follows:

The parameters referred to this function are the following:

PC67 = Maximum dynamic offset for winter operation (heat pump)

PC68 = Compensation-start temperature for dynamic winter set point

PC69 = Compensation- stop temperature for dynamic winter set point.

SP + PC67

SP

Set Point

Outdoor T

PC68

PC69

SP

SP + PC64

Set Point

Outdoor T

PC65

PC66