c-pro 3 micro CHIL | Application manual ver. 1.0 | Codice 144CP3CHE104
page 25 of 120
operation of the source pump # 2.
0: Auto – normal operation
1: Manu – manual operation
Water-Water
unit
PM47
During manual operation, it forces the
start-up/shutdown of source pump #1
0
0
1
MA-M
Only for
Water-Water
unit
PM48
During manual operation, it forces the
start-up/shutdown of source pump #2
0
0
1
MA-M
Only for
Water-Water
unit
PM51
It enables the manual/automatic
operation of the condensing fan in
Circuit # 1.
0: Auto – normal operation
1: Manu – manual operation
0
0
1
MA-M
PM52
It enables the manual/automatic
operation of the condensing fan in
Circuit # 2.
0: Auto – normal operation
1: Manu – manual operation
0
0
1
MA-M
PM61
During manual operation, it forces the
value of the condensing fan in Circuit
#1.
0
0
100
%
MA-M
With PF01=1
(Modulating
Control)
PM62
During manual operation, it forces the
value of the condensing fan in Circuit
#2.
0
0
100
%
MA-M
With PF01=1
(Modulating
Control)
PM63
During manual operation, it forces the
value of the condensing fan in Circuit
#1.
0
0
1
MA-M
With PF01=0
(Single stage
Control)
PM64
During manual operation, it forces the
value of the condensing fan in Circuit
#2.
0
0
1
MA-M
With PF01=0
(Single stage
Control)
PM65
It enables the manual/automatic
operation of the dedicated free-
ccoling fan:
0: Auto – normal operation
1: Manu – manual operation
0
0
1
MA-M
Only for
Chillers
Air-Water unit
When PG13>0
PM66
During manual operation, it forces the
value of the dedicated free-cooling
fan
0
0
100
%
MA-M
Only for
Chillers
Air-Water unit
When PG13=1
PM67
During manual operation, it forces the
value of the dedicated free-cooling
fan
0
0
1
MA-M
Only for
Chillers
Air-Water unit
When PG13=2
CALIBRATION
PM71
Calibration of external temperature
sensor
0.0
-10.0
10.0
°C
MA-C
PM72
Calibration of free-cooling input
temperature sensor
0.0
-10.0
10.0
°C
MA-C
PM73
Calibration of entering temperature
0.0
-10.0
10.0
°C
MA-C