operation of the source pump # 2.

0: Auto – normal operation

1: Manu – manual operation

Water-Water

unit

PM47

During manual operation, it forces the

start-up/shutdown of source pump #1

0

0

1

MA-M

Only for

Water-Water

unit

PM48

During manual operation, it forces the

start-up/shutdown of source pump #2

0

0

1

MA-M

Only for

Water-Water

unit

PM51

It enables the manual/automatic

operation of the condensing fan in

Circuit # 1.

0: Auto – normal operation

1: Manu – manual operation

0

0

1

MA-M

PM52

It enables the manual/automatic

operation of the condensing fan in

Circuit # 2.

0: Auto – normal operation

1: Manu – manual operation

0

0

1

MA-M

PM61

During manual operation, it forces the

value of the condensing fan in Circuit

#1.

0

0

100

%

MA-M

With PF01=1

(Modulating

Control)

PM62

During manual operation, it forces the

value of the condensing fan in Circuit

#2.

0

0

100

%

MA-M

With PF01=1

(Modulating

Control)

PM63

During manual operation, it forces the

value of the condensing fan in Circuit

#1.

0

0

1

MA-M

With PF01=0

(Single stage

Control)

PM64

During manual operation, it forces the

value of the condensing fan in Circuit

#2.

0

0

1

MA-M

With PF01=0

(Single stage

Control)

PM65

It enables the manual/automatic

operation of the dedicated free-

ccoling fan:

0: Auto – normal operation

1: Manu – manual operation

0

0

1

MA-M

Only for

Chillers

Air-Water unit

When PG13>0

PM66

During manual operation, it forces the

value of the dedicated free-cooling

fan

0

0

100

%

MA-M

Only for

Chillers

Air-Water unit

When PG13=1

PM67

During manual operation, it forces the

value of the dedicated free-cooling

fan

0

0

1

MA-M

Only for

Chillers

Air-Water unit

When PG13=2

CALIBRATION

PM71

Calibration of external temperature

sensor

0.0

-10.0

10.0

°C

MA-C

PM72

Calibration of free-cooling input

temperature sensor

0.0

-10.0

10.0

°C

MA-C

PM73

Calibration of entering temperature

0.0

-10.0

10.0

°C

MA-C