EVCO EPU2LXP1CH Installer manual User Manual
Page 24

EVCO S.p.A.
c-pro 3 micro CHIL | Application manual ver. 1.0 | Codice 144CP3CHE104
page 24 of 120
limit is exceeded, the connected
alarm is triggered.
PM31
It shows the number of operating
hours of the first pump.
0
0
9999
Hrs. x10
MA-F
PM32
It shows the number of operating
hours of the second pump.
0
0
9999
Hrs. x10
MA-F
PM33
It shows the number of operating
hours of the first source pump.
0
0
9999
Hrs. x10
MA-F
PM34
It shows the number of operating
hours of the second source pump.
0
0
9999
Hrs. x10
MA-F
PM40
It sets the maximum number of
operating hours of fans. When this
limit is exceeded, the connected
alarm is triggered.
2000
0
9999
Hrs. x10
MA-F
PM41
It shows the number of operating
hours of the first fan or of the inverter
in Circuit # 1.
0
0
9999
Hrs. x10
MA-F
PM42
It shows the number of operating
hours of the second fan or of the
inverter in Circuit # 2.
0
0
9999
Hrs. x10
MA-F
PM43
It shows the number of operating
hours of the free-coolind dedicated
fan
0
0
9999
Hrs. x10
MA-F
PM90
Last maintenance date
-
MA-F
MANUAL
PM11
PM12
PM13
PM14
PM15
PM16
It enables the manual/automatic
operation of the compressor.
0: Auto – normal operation
1: Manu – manual operation
One for each compressor.
0
0
1
MA-M
PM21
PM22
PM23
PM24
PM25
PM26
During manual operation, it forces the
start-up/shutdown of the compressor.
0: switches the compressor OFF
1: switches the compressor ON
One for each compressor.
0
0
1
MA-M
PM35
It enables the manual/automatic
operation of the pump # 1.
0: Auto – normal operation
1: Manu – manual operation
0
0
1
MA-M
PM36
It enables the manual/automatic
operation of the pump # 2.
0: Auto – normal operation
1: Manu – manual operation
0
0
1
MA-M
PM37
During manual operation, it forces the
start-up/shutdown of pump #1
0
0
1
MA-M
PM38
During manual operation, it forces the
start-up/shutdown of pump #2
0
0
1
MA-M
PM45
It enables the manual/automatic
operation of the source pump # 1.
0: Auto – normal operation
1: Manu – manual operation
0
0
1
MA-M
Only for
Water-Water
unit
PM46
It enables the manual/automatic
0
0
1
MA-M
Only for