c-pro 3 micro CHIL | Application manual ver. 1.0 | Codice 144CP3CHE104

page 108 of 120

0x06CF

1744

PF45_LinInverterFa
n

25.0

0

0.00

100.00

R/W

0x06D0

1745

PF46_LinInverterFa
n

50.0

0

0.00

100.00

R/W

0x06D1

1746

PF47_LinInverterFa
n

75.0

0

0.00

100.00

R/W

0x06D2

1747

Pd01_SetStartDefro
st

6.0

0.0

652.5

Pd01 - Setpoint start defrost

R/W

0x06D3

1748

Pd02_SetStopDefro
st

12.0

0.0

652.5

Pd02 - Setpoint stop defrost

R/W

0x06D4

1749

Pd03_WaitTimeStar
tDefrost

1200

60

9600

Pd03 - Waiting interval at defrost start

R/W

0x06D5

1750

Pd05_MaxTimeDefr
ost

300

10

600

Pd05 - Max duration of defrost

R/W

0x06D6

1751

Pd06_DrippingTime

120

0

600

Pd06 - Dripping time

R/W

0x06D7

1752

Pd07_MinTimeWaitA
fterCmp

60

0

600

Pd07 - Min time to wait after compressor restart

R/W

0x06D8

1753

Pd20_EnabDefrostC
ompensation

0

0

1

Pd20 - Enable defrost compensation

R/W

0x06D9

1754

Pd21_SetStartComp
ensation

5.0

-30.0

70.0

Pd21 - Setpoint for defrosting compensation start

R/W

0x06DA

1755

Pd22_SetStopComp
ensation

0.0

-30.0

70.0

Pd22 - Setpoint for fedrosting compensation stop

R/W

0x06DB

1756

Pd23_MaxTimeCom
pensation

3600

0

9600

Pd23 - Max waiting time at defrosting compensation
stop

R/W

0x06DC

1757

PP01_PumpOperatio
n

0

0

2

PP01 - Pump Operation

R/W

0x06DD

1758

PP02_TOnCyclic

120

1

999

PP02 - Pump ON time in cyclic working

R/W

0x06DE

1759

PP03_TOffCyclic

120

1

999

PP03 - Pump OFF time in cyclic working

R/W

0x06DF

1760

PP04_TMinPumpCo
mp

60

1

999

PP04 - Min time between ON pump and ON comp

R/W

0x06E0

1761

PP05_DelayShutdo
wnPumps

60

1

999

PP05 - Delay shutdown pumps

R/W

0x06E1

1762

PP07_ShotdownPu
mpInDefrost

0

0

1

PP07 - Shutdown pump during defrost

R/W

0x06E2

1763

PP08_DeltaHoursSw
ap

4

1

240

PP08 - Delta hours to swap pumps

R/W

0x06E3

1764

PP09_PumpOperatin
gTimeLowWater

15

0

999

PP09 - Operating time pump low water flow

R/W

0x06E4

1765

PP10_PumpOperatin
gTimeLowTemp

15

0

999

PP10 - Pump operating time at low temperature

R/W

0x06E5

1766

PP21_SourcePumpO
peration

0

0

2

R/W

0x06E6

1767

Pr01_EnableAntiFre
ezeHeater

1

0

1

Pr01 - Enable antifreeze heater

R/W

0x06E7

1768

Pr02_SetpointHeate
r

5.0

-30.0

50.0

Pr02 - Setpoint heater

R/W

0x06E8

1769

Pr03_DiffHeater

2.0

0.1

18.0

Pr03 - Differential heater

R/W

0x06E9

1770

Pr04_ForceHeaterEr
rorProbe

0

0

1

Pr04 - Forcing of anti-frost heating elements when
sensor error

R/W

0x06EA

1771

Pr05_SetpointAlarm
Antifreeze

3.0

-30.0

50.0

Pr05 - Setpoint alarm antifreeze

R/W