c-pro 3 micro CHIL | Application manual ver. 1.0 | Codice 144CP3CHE104

page 29 of 120

control only if at least one compressor

is ON.

PF03

It sets whether or not fans must

switch OFF during defrosting cycles.

No (0)

No (0)

Yes (1)

IS-F

PF07

Min. time which must elapse between

the start-ups of two different fans.

10

0

999

Sec.

IS-F

PF08

Min. time which must elapse between

the shutdowns of two different fans.

20

0

999

Sec.

IS-F

PF09

Forcing of fans in case of condensing

sensor alarm

No (0)

No (0)

Yes (1)

IS-F

With PF01=0

(Single stage

Control)

PF10

Forcing of fans in case of condensing

sensor alarm

0.0

0.0

100.0

%

IS-F

With PF01=1

(Modulating

Control)

PF11

Condensing control set point for

summer operation (chiller)

20.0

5.0

45.0

Bar

IS-F

PF12

Linear control band for condensation

in summer operation (chiller)

12.0

0.1

15.0

Bar

IS-F

PF13

Enabling of forcing to maximum

Yes (1)

No (0)

Yes (1)

IS-F

PF14

Max. forcing enabling set point in

summer operation (chiller)

26.0

15.0

45.0

Bar

IS-F

PF15

Disabling differential for max. forcing

in summer operation (chiller)

2.0

0.1

5.0

Bar

IS-F

PF16

Integral time for control of valves

(cooling)

0

0

999

Sec

IS-F

If PF16=0

Integral action

not present

PF21

Condensing control set point in winter

operation (heat pump)

9.0

0.5

15.0

Bar

IS-F

PF22

Linear control band for condensation

in winter operation (heat pump)

2.0

0.1

15.0

Bar

IS-F

PF24

Max. forcing activation set point in

winter operation (heat pump,

inverter)

3.2

0.5

20.0

Bar

IS-F

PF25

Max. forcing de-activation differential

in winter operation (heat pump,

inverter)

0.5

0.1

5.0

Bar

IS-F

PF26

Integral time for control of valves

(heat pump)

0

0

999

Sec

IS-F

If PF26=0

Integral action

not present

PF27

Min. value for condenser forcing

(inverter)

0.0

0.0

100.0

%

IS-F

PF28

Speed-up time at fan start-up

(inverter)

4

0

999

Sec.

IS-F

PF31

Lower limit for condensing linear

control (inverter)

30.0

0

PF32

%

IS-F

PF32

Upper limit for condensing linear

control (inverter)

100.0

PF31

100.0

%

IS-F

PF33

Enabling of control under the

minimum condensing limit (inverter)

Yes (1)

No (0)

Yes (1)

IS-F

PF34

Switch-off differential under the

minimum condensing limit (inverter)

2.0

0.0

5.0

Bar

IS-F

PF36

Enabling of preventilation

0: No

1: Winter only

0

0

2

IS-F

This manual is related to the following products: