EVCO EPU2LXP1CH Installer manual User Manual

Page 63

background image

EVCO S.p.A.

c-pro 3 micro CHIL | Application manual ver. 1.0 | Codice 144CP3CHE104

page 63 of 120

Mode = Operating mode (1 = Winter)

PF21 = Winter condensation control set point (SP)

PF22 = Winter condensation control differential

PF13 = Maximum speed forcing enable

PF24 = Winter maximum speed forcing set point (SPF)

PF25 = Winter maximum speed forcing differential (Y)

PF26 = Integral time PI regulator

PF27 = Inverter forcing minimum value

PF28 = Speed-up time

PF31 = Fan low-speed limit

PF32 = Fan high-speed limit

PF33 = Fan control enable above set point

PF34 = Fan switching OFF differential above set point (X)

Note. With parameters PF41, PF42, PF43, PF45, PF46 and PF47 it is possible to linearize the analog output.

Pressure

Speed

SP

SP + X

SP - diff

Low speed

High speed

Max.
speed

SPF

SPF + Y