EVCO EPU2LXP1CH Installer manual User Manual
Page 63

EVCO S.p.A.
c-pro 3 micro CHIL | Application manual ver. 1.0 | Codice 144CP3CHE104
page 63 of 120
Mode = Operating mode (1 = Winter)
PF21 = Winter condensation control set point (SP)
PF22 = Winter condensation control differential
PF13 = Maximum speed forcing enable
PF24 = Winter maximum speed forcing set point (SPF)
PF25 = Winter maximum speed forcing differential (Y)
PF26 = Integral time PI regulator
PF27 = Inverter forcing minimum value
PF28 = Speed-up time
PF31 = Fan low-speed limit
PF32 = Fan high-speed limit
PF33 = Fan control enable above set point
PF34 = Fan switching OFF differential above set point (X)
Note. With parameters PF41, PF42, PF43, PF45, PF46 and PF47 it is possible to linearize the analog output.
Pressure
Speed
SP
SP + X
SP - diff
Low speed
High speed
Max.
speed
SPF
SPF + Y