beautypg.com

EVCO EPU2LXP1CH Installer manual User Manual

Page 64

background image

EVCO S.p.A.

c-pro 3 micro CHIL | Application manual ver. 1.0 | Codice 144CP3CHE104

page 64 of 120

8.8.2

Single stage fan control

Manage a single stage control of condenser fans by a digital output for every fan.

The condenser fan is switched on when the condenser pressure exceeds the condenser setpoint + condenser pressure differential. The

condenser fan is switched off when the condenser pressure falls below the condenser setpoint, see also next picture.

Mode = Operating mode (0 = Summer)

PF11 = Summer condenser control set point (SP)

PF12 = Summer condenser control differential

The condenser fan is switched on when the condenser pressure falls below the condenser setpoint - condenser pressure differential. The

condenser fan is switched off when the condenser pressure exceeds the condenser setpoint.

Mode = Operating mode (1 = Winter)

PF21 = Winter condenser control set point (SP)

PF22 = Winter condenser control differential

8.8.3

Condenser valve control

On water-to-water machines, during summer operation, the water feeding the condensing circuit is controlled according to condensing

pressure, via a valve (this can be a two-way solenoid or motor- operated pressure-switch valve, modulating with a 0-10 V control-

generated signal). Condenser control is performed in similar fashion to fan speed control. The condenser valve control is a proportional

integral control type.

In order to utilize only a proportional control you need to only set the integral time to zero (PF16=0, PF26=0). Setting an integral time

greater than zero will provide a more precise control, the integral part is tasked with bringing the output up to speed reducing the

error introduced by the sole proportional component (by default the integral component is disabled).

8.8.4

Single condenser

On twin-circuit machines, it is possible to choose to use only one circuit to manage condensation. In order to enable this function, it is

necessary to set PG11=1. Condensing is performed by the fan in Circuit # 1, using the highest of the condensing pressure/temperature

values acquired from the respective transducers.

The activated analogue/digital output is always the one related to Circuit # 1.

Press.

Fan

PF11+ PF12

PF11

ON

PF11 = Summer condensation control set
point

PF12 = Summer condensation control
differential

OFF

Press.

PF21

PF21-PF22

ON

PF21 = Winter condensation control
set point

PF22 = Winter condensation control
differential

OFF

Fan

This manual is related to the following products: