beautypg.com

EVCO EPU2LXP1CH Installer manual User Manual

Page 26

background image

EVCO S.p.A.

c-pro 3 micro CHIL | Application manual ver. 1.0 | Codice 144CP3CHE104

page 26 of 120

sensor

PM74

Calibration of leaving temperature

sensor circuit 1

0.0

-10.0

10.0

°C

MA-C

PM75

Calibration of leaving temperature

sensor circuit 2

0.0

-10.0

10.0

°C

MA-C

PM76

Calibration of source leaving

temperature sensor circuit 1

0.0

-10.0

10.0

°C

MA-C

PM77

Calibration of source leaving

temperature sensor circuit 2

0.0

-10.0

10.0

°C

MA-C

PM78

Calibration of coil temperature sensor

circuit 1

0.0

-10.0

10.0

°C

MA-C

PM79

Calibration of coil temperature sensor

circuit 2

0.0

-10.0

10.0

°C

MA-C

PM80

Calibration of discharge compressors

temperature sensor circuit 1

0.0

-10.0

10.0

°C

MA-C

PM81

Calibration of discharge compressors

temperature sensor circuit 2

0.0

-10.0

10.0

°C

MA-C

PM82

Calibration of remote

aux.temperature sensor

0.0

-10.0

10.0

°C

MA-C

PM83

Calibration of condensing pressure

sensor circuit 1

0.0

-20.0

20.0

Bar

MA-C

PM84

Calibration of condensing pressure

sensor circuit 2

0.0

-20.0

20.0

Bar

MA-C

PM85

Calibration of evaporatorating

pressure sensor circuit 1

0.0

-20.0

20.0

Bar

MA-C

PM86

Calibration of evaporatorating

pressure sensor circuit 2

0.0

-20.0

20.0

Bar

MA-C

PM87

Calibration of unique pressure sensor

circuit 1

0.0

-20.0

20.0

Bar

MA-C

PM88

Calibration of unique pressure sensor

circuit 2

0.0

-20.0

20.0

Bar

MA-C

PSd2

It modifies the password at

Maintenance Operator level.

0

-999

9999

MA-F

Level

3

INSTALLATION MENU

COMPRESSORS

PC01

Rotation type used for compressor

management:

0: FIFO

1: LIFO

2: FIFO + hours

3: LIFO + hours

0

0

3

IS-C

PC02

Enabling mode of compressors in the

two circuits:

0: Circuit balancing

1: Circuit saturation

0

0

1

IS-C

Only on twin

circuits

PC04

Min. time for which the compressor

must remain ON, even if a shutdown

has been requested.

20

0

999

Sec.

IS-C

PC05

Min. time for which the compressor

must remain OFF, even if a start-up

has been requested.

120

0

999

Sec.

IS-C

PC06

Min. time which must elapse between

two start-ups of the same

360

0

999

Sec.

IS-C