6.4
Menu StAt (Only for display LED)
If the StAt voice is chosen from the general menu, several main statuses of the system are displayed (can be navigatedwith the
Left/Right buttons) on the reference page:
Exampletable of system statuses displayed on Page 1
Reference page
Status displayed
System status
Page 1
Unit
Indicates the status in which the machine operates (OFF, ChIL, pdC, dEFr, dRIp, F-C)
Page 1
ModE
Indicates the operational mode of the machine (ChIL, pdC)
Page 1
tdF1
Accumulation of wait time for defrost circuit 1
Page 1
dFr1
Duration of circuit defrost 1
Page 1
tdF2
Accumulation of wait time for defrost circuit 2
Page 1
dFr2
Duration of defrostcircuit 2
Page 1
SEtC
Summer mode current set point
Page 1
SEtH
Winter mode current set point
Page 1
rEGP
Main regulation probe
Page 1
PREq
Power required [%]
Page 1
PSup
Power supplied[%]
Example table of system statuses displayed on Page 2
Reference page
Status displayed
System status
Page 2
CMP1, CMP2 .. CMP6
Status of compressors (dIS, OFF, tOn, On, tOFF, ALAr, MAnU)
Page 2
FAn1, FAn 2
Status of fans (dIS, OFF, tOn, On, tOFF, ALAr, MAnU)
Page 2
InF1,InF2
Speed of condenser fans [%]
Page 2
PMP1, PMP2
Status of pumps (dIS, OFF, On, ALAr, MAnU)
Page 2
PMS1, PMS2
Status of heat source pumps (dIS, OFF, On, ALAr, MAnU)
Page 2
F-C
Status of free-cooling activation
Page 2
vF-C
Free-cooling valve
Page 2
FF-C
Free-cooling regulation
Page 2
vpC1
Status of C1splitter valve for free-cooling
Page 2
vpC2
Status of C2 splitter valve for free-cooling
Sample table of system statuses displayed on Page 3
Reference page
Status displayed
System status
Page 3
tExt
External temperature probe
Page 3
tAux
Remote temperature probe
Page 3
tiFc
Machine input temperature probe (Free-Cooling)
Page 3
tin
Heat sink exchanger input temperature probe
Page 3
toC1/2
Heat sink exchanger output temperature probe (circuit 1,2)
Page 3
toS1/2
Heat source exchanger input temperature probe (circuit 1,2)
Page 3
tCo1/2
Coil temperature probe (circuit 1,2)
Page 3
GAS1/2
Exhaust gas compressor temperature probe (circuit 1,2)
Page 3
tSu1/2
Intake compressor temperature probe (circuit 1,2)
Page 3
PCO1/2
Condensing pressure probe (circuit 1,2)
Page 3
PEV1/2
Evaporation pressure probe (circuit 1,2)
Page 3
Pun1/2
Single pressure probe (circuit 1,2)