EVCO EPU2LXP1CH Installer manual User Manual
Page 107

EVCO S.p.A.
c-pro 3 micro CHIL | Application manual ver. 1.0 | Codice 144CP3CHE104
page 107 of 120
0x06B3
1716
PF03_StopFan_Defr
ost
0
0
1
PF03- Stop fan during defrost
R/W
0x06B4
1717
PF07_Fan_TonOther
10
0
999
PF07 - Fan Min Time between 2 starts
R/W
0x06B5
1718
PF08_Fan_ToffOther
20
0
999
PF08 - Min Time between 2 fan shutdown
R/W
0x06B6
1719
PF09_ForceInErrorP
robe
0
0
1
PF09 - Fan operation in case of condensing sensor
alarm
R/W
0x06B7
1720
PF10_ForceInErrorP
robe
0.00
0.00
100.00
PF10 - Fan frequency in case of condensing sensor
alarm
R/W
0x06B8
1721
PF11_SetCond_Chill
er
20.0
5.0
652.5
PF11 - Setpoint condensation summer (Chiller)
R/W
0x06B9
1722
PF12_DiffCond_Chill
er
12.0
0.1
217.5
PF12 - Differential condensation summer (Chiller)
R/W
0x06BA
1723
PF13_EnabForceMa
x
1
0
1
PF13 - Enable force max condensation
R/W
0x06BB
1724
PF14_SetForcingMa
xCond_Chiller
26.0
15.0
652.5
PF14 - Setpoint max condenstion summer (Chiller)
R/W
0x06BC
1725
PF15_DiffForcingMa
xCond_Chiller
2.0
0.1
72.5
PF15 - Differential max condensation summer
(Chiller)
R/W
0x06BD
1726
PF16_CoolingPI
0
0
999
PF08 - Integral time for control of valves (cooling)
R/W
0x06BE
1727
PF21_SetRegCond_
HP
9.0
0.5
217.5
PF21 - Setpoint condensation winter (HP)
R/W
0x06BF
1728
PF22_DiffRegCond_
HP
2.0
0.1
217.5
PF22 - Differential condensation winter (HP)
R/W
0x06C0
1729
PF24_SetForcingMa
xCond_HP
3.2
0.5
290.0
PF24 - Setpoint max condensation winter (HP)
R/W
0x06C1
1730
PF25_DiffForcingMa
xCond_HP
0.5
0.1
72.5
PF25 - Differential max condensation winter (HP)
R/W
0x06C2
1731
PF26_HeatingPI
0
0
999
PF08 - Integral time for control of valves (heating)
R/W
0x06C3
1732
PF27_MinVal_Invert
erFan
0.00
0.00
100.00
PF27 - Min value inverter for condensing forcing
R/W
0x06C4
1733
PF28_SpeedUp_Inv
erterFan
4
0
999
PF28 - SpeedUp inverter condener
R/W
0x06C5
1734
PF31_LimitMinCond
ensationLinear
30.0
0
0.00
100.00
PF31 - Min Limit regulation inverter condensation
R/W
0x06C6
1735
PF32_LimitMaxCond
ensationLinear
100.
00
0.00
100.00
PF32 - Max Limit regulation inverter condensation
R/W
0x06C7
1736
PF33_EnabCutOff
1
0
1
PF33 - Enable fan control under min condensing
limit
R/W
0x06C8
1737
PF34_DiffCutOff
2.0
0.0
72.5
PF34 - Switch-off differential under the minimum
condensing limit (inverter)
R/W
0x06C9
1738
PF36_EnabFanPrest
art
1
0
2
0=No, 1=Winter only, 2=Always
R/W
0x06CA
1739
PF38_FanPrestartSp
eed
50.0
0
0.00
100.00
R/W
0x06CB
1740
PF39_FanPrestartTi
me
10
0
999
R/W
0x06CC
1741
PF41_LinInverterFa
n
25.0
0
0.00
100.00
R/W
0x06CD
1742
PF42_LinInverterFa
n
50.0
0
0.00
100.00
R/W
0x06CE
1743
PF43_LinInverterFa
n
75.0
0
0.00
100.00
R/W