EVCO S.p.A.
c-pro 3 micro CHIL | Application manual ver. 1.0 | Codice 144CP3CHE104
page 106 of 120
0x0699
1690
PC49_MinTimeHPTC
10
0
99
PC49 - Min. time for maintaining pressure-switch
partialization
R/W
0x069A
1691
PC50_EnabPressCo
ntrolLT
0
0
1
PC50 - Enable low-temperature pressure-switch
control (heat pump)
R/W
0x069B
1692
PC51_SetControlPre
ssostaticLP
3.2
0.0
145.0
PC51 - Pressure setpoint for low-temperature
pressure-switch control
R/W
0x069C
1693
PC52_DiffControlPre
ssostaticLT
2.0
0.0
145.0
PC52 - Differential pressure for pressostatic control
at low temperature
R/W
0x069D
1694
PC53_SetMinAirExt
-5.0
-10.0
41.0
PC53 - Setpoint low external temperature for
pressure control
R/W
0x069E
1695
PC54_SetMaxTemp
Out
48.0
30.0
158.0
PC54 - Setpoint low external temperature for
pressostaticcontro
R/W
0x069F
1696
PC55_DelayPartializ
ation
900
0
999
PC55 - Delay for partialization from low pressure
alarm
R/W
0x06A0
1697
PC61_SetCommutat
ionSummer
20.0
0.0
158.0
PC61 - Setpoint commutation summer
R/W
0x06A1
1698
PC62_SetCommutat
ionWinter
10.0
0.0
158.0
PC62 - Setpoint commutation winter
R/W
0x06A2
1699
PC64_offsetDynami
cSetSummer
-
10.0
-36.0
36.0
PC64 - Offset dynamic setpoint summer (Chiller)
R/W
0x06A3
1700
PC65_StartTempDy
namicSPSummer
30.0
-27.0
126.0
PC65 - StartTemperature Dynamic Setpoint Summer
(Chiller)
R/W
0x06A4
1701
PC66_EndTempDyn
amicSPSummer
60.0
-27.0
126.0
PC66 - End Temperature Dynamic Setpoint Summer
(Chiller)
R/W
0x06A5
1702
PC67_offsetDynami
cSetWinter
10.0
-36.0
36.0
PC67 - Offset dynamic setpoint winter (HP)
R/W
0x06A6
1703
PC68_StartTempDy
namicSPWinter
0.0
-27.0
126.0
PC68 - StartTemperature Dynamic Setpoint Winter
(HP)
R/W
0x06A7
1704
PC69_EndTempDyn
amicSPWinter
30.0
-27.0
126.0
PC66 - End Temperature Dynamic Setpoint Winter
(HP)
R/W
0x06A8
1705
PC70_FunctionLimit
Management
0
0
2
PC70 - Function limit management
R/W
0x06A9
1706
PC71_FunctionLimit
SetPoint
-7.0
-54.0
54.0
PC71 - Function limit setpoint
R/W
0x06AA
1707
PC72_FunctionLimit
Diff
4.0
0.1
18.0
PC72 - Function limit differential
R/W
0x06AB
1708
PC80_AbilitaControll
oaRichiesta
0
0
1
R/W
0x06AC
1709
PC81_SetpointContr
ollo_a_Richiesta_Es
tate
15.0
-15.0
70.0
R/W
0x06AD
1710
PC82_SetpointContr
ollo_a_Richiesta_In
verno
45.0
-15.0
70.0
R/W
0x06AE
1711
PC83_DiffControllo_
a_Richiesta_Estate
4.0
0.1
10.0
R/W
0x06AF
1712
PC84_DiffControllo_
a_Richiesta_Inverno
4.0
0.1
10.0
R/W
0x06B0
1713
PC85_RitardoContro
lloSuRichiesta
5
0
999
R/W
0x06B1
1714
PF01_CondenserCo
ntrolType
0
0
1
PF01 - Condenser control type
R/W
0x06B2
1715
PF02_EnFanWithCm
p
1
0
1
PF02 - Enable fan control only if at least one
compressor is ON
R/W