c-pro 3 micro CHIL | Application manual ver. 1.0 | Codice 144CP3CHE104

page 105 of 120

0x067E

1663

PC07_Cmp_TonOth
er

360

0

999

PC07 - Min time between 2 startup of different comp

R/W

0x067F

1664

PC08_Cmp_ToffOth
er

180

0

999

PC08 - Min time between 2 shutdown of different
comp

R/W

0x0680

1665

PC09_MaxNumEvHo
ur

8

4

12

PC09 - Max number of startups for every hour

R/W

0x0681

1666

PC10_CompressorIn
ErrorProbe

1

0

3

PC10 - Number of compressors ON for circuit during
error sensor

R/W

0x0682

1667

PC11_TypeRegulati
on

0

0

1

PC11 - Type of control

R/W

0x0683

1668

PC12_ProportionalL
ateralBand

2.5

1.0

36.0

PC12 - Proportional band lateral control

R/W

0x0684

1669

PC14_DeadZone

3.0

0.1

18.0

PC14 - Neutral zone

R/W

0x0685

1670

PC15_DeadZone_Mi
n

1.0

0.1

18.0

PC15 - Min. value of compressor zero energy band

R/W

0x0686

1671

PC16_DeadZone_M
ax

5.0

0.1

18.0

PC16 - Max. value of compressor zero energy band

R/W

0x0687

1672

PC17_DeadZoneOut
sideTime

20

0

999

PC17 - Release time compressor neutral zone
control

R/W

0x0688

1673

PC18_DeadZoneAda
ptive

0

0

1

PC18 - Enable adaptive control neutral zone control

R/W

0x0689

1674

PC21_MinValueSetC
hiller

5.0

-15.0

73.0

PC21 - Min Value Setpoint Summer (Chiller)

R/W

0x068A

1675

PC22_MaxValueSet
Chiller

20.0

15.0

73.0

PC22 - Max Value Setpoint Summer (Chiller)

R/W

0x068B

1676

PC23_MinValueSetH
P

30.0

23.0

158.0

PC23 - Min setpoint winter (HP)

R/W

0x068C

1677

PC24_MaxValueSet
HP

44.0

23.0

158.0

PC24 - Max setpoint winter (HP)

R/W

0x068D

1678

PC31_PowerLimited
Summer

50

0

100

PC31 - Power Limited Summer

R/W

0x068E

1679

PC32_PowerLimited
Winter

50

0

100

PC32 - Power Limited Winter

R/W

0x068F

1680

PC35_EnabForceSh
utDown

0

0

1

PC35 - Enable compressors force shutdown

R/W

0x0690

1681

PC36_SetForceSum
mer

3.5

-30.0

73.0

PC36 - Summer force shutdown setpoint

R/W

0x0691

1682

PC37_SetForceWint
er

52.0

26.0

167.0

PC37 - Winter force shutdown setpoint

R/W

0x0692

1683

PC41_EnabPumpDo
wn

1

0

2

PC41 - Enable Pump-Down

R/W

0x0693

1684

PC42_CompShutDo
wnTime

5

0

240

PC42 - Compressor shutdown time in pumpdown

R/W

0x0694

1685

PC43_DiffPumpDow
n

1.5

0.0

72.5

PC43 - Threshold for Pump-Down disabling

R/W

0x0695

1686

PC45_EnabHPTC

0

0

1

PC45 - Enable high-temperature pressure-switch
control

R/W

0x0696

1687

PC46_SetpointHPTC

27.0

0.0

652.5

PC46 - Pressure set point for high-temperature
pressure-switch control

R/W

0x0697

1688

PC47_DiffHPTC

2.0

0.0

72.5

PC47 - Pressure differential for high-temperature
pressure-switch control

R/W

0x0698

1689

PC48_ThresholdAirE
xtHPTC

12.0

-30.0

73.0

PC48 - External high temperature threshold for
pressure-switch control

R/W