EVCO EPU2LXP1CH Installer manual User Manual
Page 105

EVCO S.p.A.
c-pro 3 micro CHIL | Application manual ver. 1.0 | Codice 144CP3CHE104
page 105 of 120
0x067E
1663
PC07_Cmp_TonOth
er
360
0
999
PC07 - Min time between 2 startup of different comp
R/W
0x067F
1664
PC08_Cmp_ToffOth
er
180
0
999
PC08 - Min time between 2 shutdown of different
comp
R/W
0x0680
1665
PC09_MaxNumEvHo
ur
8
4
12
PC09 - Max number of startups for every hour
R/W
0x0681
1666
PC10_CompressorIn
ErrorProbe
1
0
3
PC10 - Number of compressors ON for circuit during
error sensor
R/W
0x0682
1667
PC11_TypeRegulati
on
0
0
1
PC11 - Type of control
R/W
0x0683
1668
PC12_ProportionalL
ateralBand
2.5
1.0
36.0
PC12 - Proportional band lateral control
R/W
0x0684
1669
PC14_DeadZone
3.0
0.1
18.0
PC14 - Neutral zone
R/W
0x0685
1670
PC15_DeadZone_Mi
n
1.0
0.1
18.0
PC15 - Min. value of compressor zero energy band
R/W
0x0686
1671
PC16_DeadZone_M
ax
5.0
0.1
18.0
PC16 - Max. value of compressor zero energy band
R/W
0x0687
1672
PC17_DeadZoneOut
sideTime
20
0
999
PC17 - Release time compressor neutral zone
control
R/W
0x0688
1673
PC18_DeadZoneAda
ptive
0
0
1
PC18 - Enable adaptive control neutral zone control
R/W
0x0689
1674
PC21_MinValueSetC
hiller
5.0
-15.0
73.0
PC21 - Min Value Setpoint Summer (Chiller)
R/W
0x068A
1675
PC22_MaxValueSet
Chiller
20.0
15.0
73.0
PC22 - Max Value Setpoint Summer (Chiller)
R/W
0x068B
1676
PC23_MinValueSetH
P
30.0
23.0
158.0
PC23 - Min setpoint winter (HP)
R/W
0x068C
1677
PC24_MaxValueSet
HP
44.0
23.0
158.0
PC24 - Max setpoint winter (HP)
R/W
0x068D
1678
PC31_PowerLimited
Summer
50
0
100
PC31 - Power Limited Summer
R/W
0x068E
1679
PC32_PowerLimited
Winter
50
0
100
PC32 - Power Limited Winter
R/W
0x068F
1680
PC35_EnabForceSh
utDown
0
0
1
PC35 - Enable compressors force shutdown
R/W
0x0690
1681
PC36_SetForceSum
mer
3.5
-30.0
73.0
PC36 - Summer force shutdown setpoint
R/W
0x0691
1682
PC37_SetForceWint
er
52.0
26.0
167.0
PC37 - Winter force shutdown setpoint
R/W
0x0692
1683
PC41_EnabPumpDo
wn
1
0
2
PC41 - Enable Pump-Down
R/W
0x0693
1684
PC42_CompShutDo
wnTime
5
0
240
PC42 - Compressor shutdown time in pumpdown
R/W
0x0694
1685
PC43_DiffPumpDow
n
1.5
0.0
72.5
PC43 - Threshold for Pump-Down disabling
R/W
0x0695
1686
PC45_EnabHPTC
0
0
1
PC45 - Enable high-temperature pressure-switch
control
R/W
0x0696
1687
PC46_SetpointHPTC
27.0
0.0
652.5
PC46 - Pressure set point for high-temperature
pressure-switch control
R/W
0x0697
1688
PC47_DiffHPTC
2.0
0.0
72.5
PC47 - Pressure differential for high-temperature
pressure-switch control
R/W
0x0698
1689
PC48_ThresholdAirE
xtHPTC
12.0
-30.0
73.0
PC48 - External high temperature threshold for
pressure-switch control
R/W