beautypg.com

EVCO EPU2LXP1CH Installer manual User Manual

Page 74

background image

EVCO S.p.A.

c-pro 3 micro CHIL | Application manual ver. 1.0 | Codice 144CP3CHE104

page 74 of 120

PA13 = Low-pressure alarm by-pass time

PA14 = Maximum number of auto-reset low-pressure alarms

If, with the machine switched ON and in the presence of a request for chill from the controller, low pressure is detected, compressor

start-up is inhibited and a Start-up low-pressure alarm AL21 (and AL22 for Circuit # 2) is displayed. The purpose of this condition is

to inhibit compressor start-up in the absence of Freon® gas in the circuit (there could be a refrigerant leak from the piping system

8.17.4

Management of low-pressure transducer alarm (heat pump mode)

If intake pressure falls below a given threshold, a low-pressure alarm AL41 (and AL42 for Circuit # 2) is generated. The alarm causes

the immediate stopping of the refrigerating circuit, also shutting down any compressors which may be ON, and inhibiting the start-up of

others.

At start-up of the first compressor, the alarm is delayed for a given interval, to enable the compressors to take the refrigerating circuit

to full pressure.

The alarm is initially auto-resetting, unless it exceeds a given number of events within one hour (PA14), in which case it becomes a

manual-reset alarm, which can be reset if in the meantime pressure has risen above the minimum threshold by a certain differential

value.

PA11 = Low-pressure alarm set point

PA12 = Low-pressure alarm differential

PA13 = Low-pressure alarm by-pass time

PA14 = Maximum number of auto-reset low-pressure alarms

In the presence of low temperatures of external air, intake pressure could fall below the minimum- pressure threshold, thus inhibiting

compressor start-up. In such a situation, it is possible to activate a control, which shifts the alarm-control threshold to a higher value

for a given interval from start-up of the first compressor, leaving nevertheless in place all protection devices and pre-start checks.

PA16 = Low-pressure control enable at low outdoor air temperature

PA17 = Low-pressure alarm set point at low outdoor air temperature

PA18 = Low-pressure alarm differential at low outdoor air temperature

PA19 = Low-pressure alarm control duration at low outdoor air temperature

This control can only be enabled in heat-pump operating mode.

8.17.5

Low start-up pressure alarm

In a low-pressure condition (pressure switch or transducer-induced) and in the impossibility to activate any of the compressors at the

request of the same, there is a Low-pressure start-up alarm AL51 (and AL52 for Circuit # 2). This is an auto-reset alarm, and thus

should disappear, unless there is a leak of Freon® gas from the circuit.

At compressor shutdown following a low-pressure alarm, this alarm is delayed by a given interval PA20, to give the refrigerating circuit

the chance to enable compressor start-up.

This manual is related to the following products: