EVCO EPU2LXP1CH Installer manual User Manual
Page 30

EVCO S.p.A.
c-pro 3 micro CHIL | Application manual ver. 1.0 | Codice 144CP3CHE104
page 30 of 120
2: Always
PF38
Preventilation speed
50.0
0.0
100.0
%
IS-F
With PF01=1
(Modulating
Control)
PF39
Preventilation time
10
0
999
Sec
IS-F
PF41
Value x1 of fan linearization table
25.0
0.0
PF42
%
IS-F
PF42
Value x2 of fan linearization table
50.0
PF41
PF43
%
IS-F
PF43
Value x3 of fan linearization table
75.0
PF42
100.0
%
IS-F
PF45
Value y1 of fan linearization table
25.0
0.0
PF46
%
IS-F
PF46
Value y2 of fan linearization table
50.0
PF45
PF47
%
IS-F
PF47
Value y3 of fan linearization table
75.0
PF46
100.0
%
IS-F
DEFROST
Only for Air-
Water unit
Pd01
Pressure set point at defrosting start
6.0
0.0
Pd02
Bar
IS-D
Pd02
Pressure set point at defrosting stop
12.0
Pd01
45.0
Bar
IS-D
Pd03
Waiting interval at defrosting start
1200
60
Pd23
Sec.
IS-D
Pd05
Max. duration of defrosting
300
10
600
Sec.
IS-D
Pd06
Duration of dripping
120
0
600
Sec.
IS-D
Pd07
Min. defrost waiting interval after
compressor re-start
60
0
600
Sec.
IS-D
Pd20
Enabling of defrosting cycle
compensation
No (0)
No (0)
Yes (1)
IS-D
Pd21
Outdoor air temperature set point for
defrosting compensation start
5.0
Pd22
70.0
IS-D
Pd22
Outdoor air temperature set point for
defrosting compensation stop
0.0
-30.0
Pd21
IS-D
Pd23
Max. waiting interval at defrosting
stop
3600
Pd03
9600
IS-D
PUMPS
PP01
Pump operation:
0 = Continuous operation
1 = Operation at thermostat’s request
2 = Cyclical operation
0
0
2
IS-P
PP02
ON time in cyclical operation
120
1
999
Sec.
IS-P
PP03
OFF time in cyclical operation
120
1
999
Sec.
IS-P
PP04
Min. interval which must elapse
between pump start-up and first
compressor
60
1
999
Sec.
IS-P
PP05
Min. interval which must elapse
between circuit shutdown and pump
60
1
999
Sec.
IS-P
PP07
Shutdown of pump during defrosting
No (1)
No (0)
Yes (1)
IS-P
PP08
Difference in operating hours between
the two pumps, requiring their being
swapped.
4
1
240
Hours
IS-P
PP09
Pump operating time at low water
flow (flow alarm)
15
0
999
Sec.
IS-P
PP10
Pump operating time at low
temperature of outflow water (anti-
frost alarm)
15
0
999
Sec.
IS-P
PP21
Source Pump operation:
0= Continuous operation
1=Operation at thermostat’s request
2 = Cyclical operation
0
0
2
IS-P
Only for
Water-Water
unit
ANTI-FREEZE