c-pro 3 micro CHIL | Application manual ver. 1.0 | Codice 144CP3CHE104

page 30 of 120

2: Always

PF38

Preventilation speed

50.0

0.0

100.0

%

IS-F

With PF01=1

(Modulating

Control)

PF39

Preventilation time

10

0

999

Sec

IS-F

PF41

Value x1 of fan linearization table

25.0

0.0

PF42

%

IS-F

PF42

Value x2 of fan linearization table

50.0

PF41

PF43

%

IS-F

PF43

Value x3 of fan linearization table

75.0

PF42

100.0

%

IS-F

PF45

Value y1 of fan linearization table

25.0

0.0

PF46

%

IS-F

PF46

Value y2 of fan linearization table

50.0

PF45

PF47

%

IS-F

PF47

Value y3 of fan linearization table

75.0

PF46

100.0

%

IS-F

DEFROST

Only for Air-
Water unit

Pd01

Pressure set point at defrosting start

6.0

0.0

Pd02

Bar

IS-D

Pd02

Pressure set point at defrosting stop

12.0

Pd01

45.0

Bar

IS-D

Pd03

Waiting interval at defrosting start

1200

60

Pd23

Sec.

IS-D

Pd05

Max. duration of defrosting

300

10

600

Sec.

IS-D

Pd06

Duration of dripping

120

0

600

Sec.

IS-D

Pd07

Min. defrost waiting interval after

compressor re-start

60

0

600

Sec.

IS-D

Pd20

Enabling of defrosting cycle

compensation

No (0)

No (0)

Yes (1)

IS-D

Pd21

Outdoor air temperature set point for

defrosting compensation start

5.0

Pd22

70.0

IS-D

Pd22

Outdoor air temperature set point for

defrosting compensation stop

0.0

-30.0

Pd21

IS-D

Pd23

Max. waiting interval at defrosting

stop

3600

Pd03

9600

IS-D

PUMPS

PP01

Pump operation:

0 = Continuous operation

1 = Operation at thermostat’s request

2 = Cyclical operation

0

0

2

IS-P

PP02

ON time in cyclical operation

120

1

999

Sec.

IS-P

PP03

OFF time in cyclical operation

120

1

999

Sec.

IS-P

PP04

Min. interval which must elapse

between pump start-up and first

compressor

60

1

999

Sec.

IS-P

PP05

Min. interval which must elapse

between circuit shutdown and pump

60

1

999

Sec.

IS-P

PP07

Shutdown of pump during defrosting

No (1)

No (0)

Yes (1)

IS-P

PP08

Difference in operating hours between

the two pumps, requiring their being

swapped.

4

1

240

Hours

IS-P

PP09

Pump operating time at low water

flow (flow alarm)

15

0

999

Sec.

IS-P

PP10

Pump operating time at low

temperature of outflow water (anti-

frost alarm)

15

0

999

Sec.

IS-P

PP21

Source Pump operation:

0= Continuous operation

1=Operation at thermostat’s request

2 = Cyclical operation

0

0

2

IS-P

Only for

Water-Water

unit

ANTI-FREEZE