c-pro 3 micro CHIL | Application manual ver. 1.0 | Codice 144CP3CHE104
page 46 of 120
8.2.2
Water-To-Water Chiller
PGUT=2 (1 Circuit)
PGUT=10 (2 Circuit)
Controller Analog Inputs
A/I 1
Heat sink exchanger input temperature
Heat sink exchanger input temperature
A/I 2
Heat sink exchanger output temperature
Heat sink exchanger output temperature
A/I 3
Condensing pressure C1 (4-20mA)
Condensing pressure C1 (4-20mA)
A/I 4
Compressor discharge temperature C1
Compressor discharge temperature C1
Expansion Analog Inputs
A/I 1
Not present
Condensing pressure C2 (4-20mA)
A/I 2
Not present
Compressor discharge temperature C2
Controller Digital Inputs
D/I 1
On/Off
On/Off
D/I 2
Heat sink exchanger flow meter
Heat sink exchanger flow meter
D/I 3
Heat sink heat pump 1
Heat sink heat pump 1
D/I 4
Thermal compressor 2
Thermal compressor 2
D/I 5
High pressure C1
High pressure C1
D/I 6
Low pressure C1
Low pressure C1
D/I 7
Thermal compressor 1
Thermal compressor 1
D/I 8
Heat source heat pump 1
Heat source heat pump 1
D/I 9
Heat source exchanger flow meter
Heat source exchanger flow meter
Expansion Digital Inputs
D/I 1
Not present
Thermal compressor 5
D/I 2
Not present
High pressure C2
D/I 3
Not present
Low pressure C2
D/I 4
Not present
Thermal compressor 4
Controller Analog Outputs
A/O 1
Water valve C1 (0-10V)
Water valve C1 (0-10V)
A/O 2
Not used
Water valve C2 (0-10V)
Expansion Analog Outputs
A/O
Not present
Not used
Controller Digital Outputs
D/O 1
Heat sink pump 1
Heat sink pump 1
D/O 2
Compressor 1
Compressor 1
D/O 3
Compressor 2
Compressor 2
D/O 4
Heat sink anti-frost resistance C1
Heat sink anti-frost resistance C1
D/O 5
Heat source pump
Heat source pump
D/O 6
Solenoid valve C1
Solenoid valve C1
Expansion Digital Outputs
D/O 1
Not present
Compressor 4
D/O 2
Not present
Compressor 5
D/O 3
Not present
Solenoid valve C2