c-pro 3 micro CHIL | Application manual ver. 1.0 | Codice 144CP3CHE104

page 32 of 120

during winter operation (heat pump)

PA07

Triggering delay for temperature

alarm

30

1

999

Sec.

IS-S

PA08

Consequent time for a temperature

alarm:

0 = Notification only

1 = Machine stop

0

0

1

Sec.

IS-S

PA09

Reset differential for temperature

alarm

0.5

0.1

10.0

°C

IS-S

PA10

Temperature alarm inhibition interval

from system start-up

15

0

999

Sec.

IS-S

PA11

Low-pressure alarm threshold during

winter operation (heat pump)

3.0

0.1

9.9

Bar

IS-S

PA12

Low-pressure alarm reset differential

during winter operation (heat pump)

1.0

0.1

4.0

Bar

IS-S

PA13

Low-pressure alarm by-pass interval

from start-up of first compressor

120

0

999

Sec.

IS-S

PA14

Number of triggered low-pressure

alarms with auto-reset before the

alarm becomes manual

3

0

5

IS-S

PA16

Enabling of low-pressure control at

start-up and at low temperatures

Yes (1)

No (0)

Yes (1)

IS-S

PA17

Low-pressure alarm threshold at

start-up and at low temperatures

1.0

0.1

9.9

Bar

IS-S

PA18

Low-pressure alarm reset differential

at start-up and at low temperatures

0.5

0.1

4.0

Bar

IS-S

PA19

Control duration at triggering of low-

pressure alarm at low temperatures

120

10

PA13

Sec.

IS-S

PA20

Min. duration of alarm delay for

triggering of low-pressure alarm at

compressor start-up

240

0

999

Sec.

IS-S

PA21

High-pressure alarm threshold

28.0

0.0

45.0

Bar

IS-S

PA22

High-pressure alarm reset differential

5.0

0.1

30.0

Bar

IS-S

PA25

Enabling of primary exchanger

efficiency alarm

No (0)

No (0)

Yes (1)

IS-S

PA26

Min. difference threshold for primary

exchanger

2.0

0.1

20.0

°C

IS-S

PA27

By-pass time for primary exchanger

efficiency alarm

120

0

999

Sec.

IS-S

PA30

Enable RTC alarm

Yes (1)

No (0)

Yes (1)

IS-S

PA31

It sets the type of reset of RTC alarm

restoration

0: Auto - Automatic

1: Manu - Manual

M

A (0)

M (1)

IS-S

PA32

It sets the triggering delay connected

with the free-cooling fan thermal

alarm

10

0

999

Sec.

IS-S

PA33

It sets the type of reset for the free-

cooling fan thermal alarm

0: A - Automatic

1: M – Manual

M

A (0)

M (1)

IS-S

PA40

It enables the alarm connected with

operating hours of compressors

Yes (1)

No (0)

Yes (1)

IS-S

PA41

It sets the triggering delay connected

10

0

999

Sec.

IS-S