c-pro 3 micro CHIL | Application manual ver. 1.0 | Codice 144CP3CHE104

page 40 of 120

6= solenoid valve

7= solenoid valve + alarms

8= resyncro

PV67

Probe type 3:

0= NTC

1= PT1000

0

0

1

CO-V

PV68

Probe type 4:

0= 4..20mA (0.5 – 8)

1= 4..20mA (0 – 30)

2= 0-5V (0 – 7)

3= 0-5V (0 – 25)

4= 0-5V (0 – 60)

5= scaling

0

0

1

CO-V

PV69

Probe type 1:

1= PTC

2= NTC

3= 0..20mA

4= 4..20mA

5= 0-5V

6= 0-10V

7= PT1000

8= NTC K2

9= NTC K3

5

1

9

CO-V

PV70

Probe type 2:

1= PTC

2= NTC

3= 0..20mA

4= 4..20mA

5= 0-5V

6= 0-10V

7= PT1000

8= NTC K2

9= NTC K3

2

1

9

CO-V

PV71

Ts offset

0.0

-10.0

10.0

K

CO-V

PV72

Te offset

0.0

-10.0

10.0

K

CO-V

PV74

Relay logic

N.O. (0)

N.O. (0)

N.C. (1)

CO-V

PV75

DI1 logic

N.O. (0)

N.O. (0)

N.C. (1)

CO-V

PV76

DI2 logic

N.O. (0)

N.O. (0)

N.C. (1)

CO-V

PV77

DI3 logic

N.O. (0)

N.O. (0)

N.C. (1)

CO-V

PV89

Enable Modulating Super-Heat

Setpoint circuit 2

Yes (1)

No (0)

Yes (1)

CO-V

PV85

Max Super-Heat circuit 2

15.0

3.0

25.0

°K

CO-V

PV86

Min Super-Heat circuit 2

2.0

1.0

25.0

°K

CO-V

PV87

Max discharge super-heat circuit 2

35.0

0.0

50.0

°K

CO-V

PV88

Min discharge super-heat circuit 2

5.0

0.0

50.0

°K

CO-V

Note: Once the machine parameters have been configured, and every time the configuration parameters are modified, it is advisable to

shut down the machine and restart the plant, to enable the card to reconfigure itself correctly.