c-pro 3 micro CHIL | Application manual ver. 1.0 | Codice 144CP3CHE104
page 40 of 120
6= solenoid valve
7= solenoid valve + alarms
8= resyncro
PV67
Probe type 3:
0= NTC
1= PT1000
0
0
1
CO-V
PV68
Probe type 4:
0= 4..20mA (0.5 – 8)
1= 4..20mA (0 – 30)
2= 0-5V (0 – 7)
3= 0-5V (0 – 25)
4= 0-5V (0 – 60)
5= scaling
0
0
1
CO-V
PV69
Probe type 1:
1= PTC
2= NTC
3= 0..20mA
4= 4..20mA
5= 0-5V
6= 0-10V
7= PT1000
8= NTC K2
9= NTC K3
5
1
9
CO-V
PV70
Probe type 2:
1= PTC
2= NTC
3= 0..20mA
4= 4..20mA
5= 0-5V
6= 0-10V
7= PT1000
8= NTC K2
9= NTC K3
2
1
9
CO-V
PV71
Ts offset
0.0
-10.0
10.0
K
CO-V
PV72
Te offset
0.0
-10.0
10.0
K
CO-V
PV74
Relay logic
N.O. (0)
N.O. (0)
N.C. (1)
CO-V
PV75
DI1 logic
N.O. (0)
N.O. (0)
N.C. (1)
CO-V
PV76
DI2 logic
N.O. (0)
N.O. (0)
N.C. (1)
CO-V
PV77
DI3 logic
N.O. (0)
N.O. (0)
N.C. (1)
CO-V
PV89
Enable Modulating Super-Heat
Setpoint circuit 2
Yes (1)
No (0)
Yes (1)
CO-V
PV85
Max Super-Heat circuit 2
15.0
3.0
25.0
°K
CO-V
PV86
Min Super-Heat circuit 2
2.0
1.0
25.0
°K
CO-V
PV87
Max discharge super-heat circuit 2
35.0
0.0
50.0
°K
CO-V
PV88
Min discharge super-heat circuit 2
5.0
0.0
50.0
°K
CO-V
Note: Once the machine parameters have been configured, and every time the configuration parameters are modified, it is advisable to
shut down the machine and restart the plant, to enable the card to reconfigure itself correctly.