8.11

Circulating Source Pump Management

On WATER-TO-WATER machines, 1 or 2 source water-circulating pumps can be controlled, which are defined by the parameter PG10.

The Pump operation PP21 parameter defines how the pump will operate.

Regulations, status, flow meter controls and safeties for these devices are the same as of the circulating pumps describedabove.

8.12

Defrosting Management

This procedure is only activated in winter operating mode (heat pump), and when at least one compressor is switched ON. Defrosting is

performed by intervening on the refrigerating-circuit inverter valve.

If evaporation pressure remains (even if not continuously), for a time interval equal to the value of parameter Defrosting enable delay

Pd03, below the threshold of the Defrosting start set point Pd01 and at least one compressor is in operation, the inverter valve is

commutated and the defrosting cycle is started. During this phase, compressors are forced to maximum power, and the low-pressure

alarm is bypassed.

Defrosting is interrupted for one of the following causes:

When pressure reaches the End of defrosting set point Pd02;

When the Defrosting duration max. time Pd05 has elapsed;

When machine or circuit alarms have been triggered;

When the unit has been switched OFF.

At the end of the defrosting cycle, the unit remains stationary for the whole duration of Dripping time Pd06.

II

In order to avoid the immediate start of a defrosting cycle after all compressors have been stopped, a Minimum circuit restart delay

Pd07 is used, which guarantees at least a period of heat-pump operation, before entering the defrosting cycle.

Note: In the case of twin-circuit units, defrosting cannot be simultaneous; thus, if one circuit is defrosting, the other circuit cannot start

a defrosting cycle until the defrosting circuit has completely finished its cycle.

Pressure

Pd02

Pd01

Pd03

Pd04

Inverter valve

Pd06

Defrost

Dripp.