c-pro 3 micro CHIL | Application manual ver. 1.0 | Codice 144CP3CHE104

page 48 of 120

D/O 2

Not present

Compressor 5

D/O 3

Not present

Reversing valve C2

Digital OutputsEVDRIVE03 circuit 1

D/O VCM 1

Solenoid valve C1

Solenoid valve C1

Digital OutputsEVDRIVE03 circuit 2

D/O VCM 2

Not present

Solenoid valve C2

8.2.4

Water-To-Water Chiller+Heat Pump

PGUT=4 (1 Circuit)

PGUT=12 (2 Circuit)

Controller Analog Inputs

A/I 1

Heat sink exchanger input temperature

Heat sink exchanger input temperature

A/I 2

Heat sink exchanger output temperature

Heat sink exchanger output temperature

A/I 3

Single pressure (4-20mA) C1

Single pressure (4-20mA) C1

A/I 4

Compressor discharge temperature C1

Compressor discharge temperature C1

A/I 5

Heat source exchanger output temperature

Heat source exchanger output temperature

A/I 6

Heat source exchanger flow meter

Not used

Expansion Analog Inputs

A/I 1

Not present

Single pressure (4-20mA) C2

A/I 2

Not present

Compressor discharge temperature C2

Controller Digital Inputs

D/I 1

On/Off

On/Off

D/I 2

Heat sink exchanger flow meter

Heat sink exchanger flow meter

D/I 3

Heat sink heat pump 1

Heat sink heat pump 1

D/I 4

Thermal compressor 2

Thermal compressor 2

D/I 5

High pressure C1

High pressure C1

D/I 6

Low pressure C1

Low pressure C1

D/I 7

Thermal compressor 1

Thermal compressor 1

D/I 8

Heat source heat pump 1

Heat source heat pump 1

D/I 9

Summer/Winter

Summer/Winter

Expansion Digital Inputs

D/I 1

Not present

Thermal compressor 5

D/I 2

Not present

High pressure C2

D/I 3

Not present

Low pressure C2

D/I 4

Not present

Thermal compressor 4

D/I 5

Not present

Heat source exchanger flow meter

Controller Analog Outputs

A/O 1

Water valveC1 (0-10V)

Water valveC1 (0-10V)

A/O 2

Not used

Water valveC2 (0-10V)

Expansion Analog Outputs

A/O

Not present

Not used

Controller Digital Outputs

D/O 1

Heat sink heat pump 1

Heat sink heat pump 1

D/O 2

Compressor 1

Compressor 1

D/O 3

Compressor 2

Compressor 2

D/O 4

Heat sink anti-frost resistance C1

Heat sink anti-frost resistance C1

D/O 5

Heat source pump

Heat source pump

D/O 6

Solenoid valve C1

Solenoid valve C1

D/O 7

Reversing valve C1

Reversing valve C1

D/O 8

Heat source anti-frost resistance C1

Heat source anti-frost resistance C1

Expansion Digital Outputs

D/O 1

Not present

Compressor 4

D/O 2

Not present

Compressor 5