Apply the motor cable shield clamp – Rockwell Automation 2097-Vxxx Kinetix 300 EtherNet/IP Indexing Servo Drive User Manual User Manual
Page 76
76
Rockwell Automation Publication 2097-UM001D-EN-P - November 2012
Chapter 4
Connecting the Kinetix 300 Drive System
Apply the Motor Cable Shield
Clamp
This procedure assumes you have completed wiring your motor power (MP)
connector and are ready to apply the cable shield clamp.
Follow these steps to apply the motor cable shield clamp.
1. Locate a suitable position for installing cable shield clamp within
50…75 mm (2…3 in.) of the drive.
2. Lay out and drill holes for cable clamp.
3. Locate the position on the motor power cable that comes under the clamp
and remove about an inch of the cable jacket to expose the shield braid.
4. Position the exposed portion of the cable braid directly in line with the
clamp.
5. Clamp the exposed shield to the panel by using the clamp and 2 #6-32 x 1
screws provided.
for each Kinetix 300 drive you are installing.
50…75
(2…3)
50…75
(2…3)
34.0
(1.34)
25
(1.0)
12.7
(0.50)
If panel is painted, remove paint to
provide metal-to-metal contact.
Motor Power Ground
Shield Clamp
Dimensions are in mm (in.).
ATTENTION: Plan the installation of your system so that you can
perform all cutting, drilling, tapping, and welding with the system
removed from the enclosure. Because the system is of the open type
construction, be careful to keep any metal debris from falling into it.
Metal debris or other foreign matter can become lodged in the circuitry,
which can result in damage to components.