Rockwell Automation Publication 2097-UM001D-EN-P - November 2012

137

Configure and Start Up the Kinetix 300 Drive

Chapter 6

The New Module dialog box opens.

4. Configure the new module.

a. Name the module.
b. Set the drive Ethernet address.

Set the Ethernet address in the software to match the Ethernet address
scrolling on the drive. See

Current IP Address Ethernet Setting

on

page 129

.

5. Click the Connection tab.

6. Configure the Requested Packet Interval (RPI) for your application.

The default setting is 20 ms. Yours could be different.

7. Click Ok.

Download the Program

After completing the Logix configuration you must download your program to
the Logix processor.