Rockwell Automation Publication 2097-UM001D-EN-P - November 2012

25

Installing the Kinetix 300 Drive System

Chapter 2

Minimum Clearance Requirements

This section provides information to assist you in sizing your cabinet and
positioning your Kinetix 300 system components.

Figure 2

illustrates minimum clearance requirements for proper airflow and

installation:

Additional clearance is required depending on the accessory items

installed.

An additional 9.7 mm (0.38 in.) clearance is required left of the drive if the

I/O expansion terminal block is used.

An additional 26 mm (1.0 in.) clearance is required right of the drive when

the heatsink is present.

An additional 36 mm (1.42 in.) is required right of the drive when the

side-mount line filter is present. An additional 50 mm (2.0 in.) is required
behind the drive when the rear-mount line filter is present.

An additional 5.0 mm (0.19 in.) clearance is required in front of the drive

when the 2090-K2CK-D15M feedback connector kit is used.

Additional clearance is required for the cables and wires connected to the

top, front, and bottom of the drive.

An additional 150 mm (6.0 in.) is required when the drive is mounted

adjacent to noise sensitive equipment or clean wireways.

See Kinetix Servo Drives Specifications Technical Data, publication

GMC -TD003

for Kinetix 300 drive dimensions.

Figure 2 - Minimum Clearance Requirements

IMPORTANT

Mount the module in an upright position as shown. Do not mount the drive
module on its side.

00

300

A

25.0 mm (1.0 in.) Clearance

for Airflow and Installation

3 mm (0.12 in.)
Side Clearance

3 mm (0.12 in.)

Side Clearance

25.0 mm (1.0 in.) Clearance

for Airflow and Installation

Drive
Cat. No.

A

2097-V31PR0

185 (7.29)

2097-V31PR2

185 (7.29)

2097-V32PR0

230 (9.04)

2097-V32PR2

230 (9.04)

2097-V32PR4

230 (9.04)

2097-V33PR1

185 (7.29)

2097-V33PR3

185 (7.29)

2097-V33PR5

185 (7.29)

2097-V33PR6

230 (9.04)

2097-V34PR3

185 (7.29)

2097-V34PR5

185 (7.29)

2097-V34PR6

230 (9.04)