beautypg.com

Wiring the kinetix 300 drive connectors, Wire the safe torque-off (sto) connector, Wire the back-up power (bp) connector – Rockwell Automation 2097-Vxxx Kinetix 300 EtherNet/IP Indexing Servo Drive User Manual User Manual

Page 69

background image

Rockwell Automation Publication 2097-UM001D-EN-P - November 2012

69

Connecting the Kinetix 300 Drive System

Chapter 4

Wiring the Kinetix 300 Drive
Connectors

This section provides examples and wiring tables to assist you in making
connections to the Kinetix 300 drive.

Wire the Safe Torque-off (STO) Connector

For the safe torque-off (STO) connector pinouts, feature descriptions, and wiring
information, see Chapter 8 on

page 159.

Wire the Back-up Power (BP) Connector

Table 26 - Back-up Power (BP) Connector

+

24

-

+24V DC

RETURN

Kinetix 300 Drive, Front View

Drive Cat. No.

Terminals

Recommended
Wire Size
mm

2

(AWG)

Strip Length
mm (in.)

Torque Value
N•m (lb•in)

2097-V3xPRx

+24V DC

1.5 (16)

6 (0.25)

0.5 (4.5)

-24V DC