Standard analog outputs – Rockwell Automation 1755-OF8 GuardPLC Controller Systems User Manual
Page 97
Publication 1753-UM001C-EN-P - March 2010
97
Wire the 1753-IF8XOF4 Analog I/O Module Chapter 9
Standard Analog Outputs
The module has 4 analog outputs, which are not safety-rated outputs.
However, in the event of an internal error, they can be shut down
safely through configuration via the user program.
When you are not using the analog outputs, use RSLogix Guard PLUS!
programming software to set the 4 analog output (USED) system
signals to FALSE. When set to FALSE, no output signals are transmitted
when the safety switches are opened. Alternatively, you can set the
analog outputs to zero by using the Emergency Off system variable.
These are the analog output resolution options.
19
T7
Sensor supply 7
20
I7
Analog input 7
21
L-
Reference pole input 7
22
T8
Sensor supply 8
23
I8
Analog input 8
24
L-
Reference pole input 8
Terminal Number
Designation
Function
ATTENTION
To achieve SIL 3, the output values must be read back via safety
analog inputs and evaluated in the RSLogix Guard PLUS! user
program. Appropriate reactions to incorrect output values must
be applied. Otherwise, they may not be used as safety outputs.
Value Range in the Application
Output Current
0
0 mA
2000
20 mA
- 1755-HSC GuardPLC Controller Systems 1755-IF8 GuardPLC Controller Systems 1755-IB24XOB16 GuardPLC Controller Systems 1755-A6 GuardPLC Controller Systems 1755-L1 GuardPLC Controller Systems 1754-L28BBB GuardPLC Controller Systems 1753-IB20XOB8 GuardPLC Controller Systems 1753-OB16 GuardPLC Controller Systems 1753-IB16 GuardPLC Controller Systems 1753-L32BBBP-8A GuardPLC Controller Systems 1753-L32BBBM-8A GuardPLC Controller Systems 1753-L28BBBP GuardPLC Controller Systems 1753-L28BBBM GuardPLC Controller Systems