1755-ib24xob16 module status indicators, Serial communication indicators, Power supply and module status – Rockwell Automation 1755-OF8 GuardPLC Controller Systems User Manual
Page 147
![background image](/manuals/579232/147/background.png)
Publication 1753-UM001C-EN-P - March 2010
147
Diagnostics Chapter 15
Serial Communication Indicators
1755-IB24XOB16 Module
Status Indicators
The 1755-IB24XOB16 digital combination input and output module
(AB-DIO) has status indicators for:
•
power supply.
•
module status.
•
I/O status.
Power Supply and Module Status
Indicator
Status
Description
FB1
On
Field bus no. 1 is active
FB2
On
Field bus no. 2 is active
(serial interface module)
IMPORTANT
Only the bottom serial port on the GuardPLC 2000 controller is
active, as indicated by the FB2 status indicator.
FB1
FB2
RUN ERR
1755-
IB24XOB16
RUN ERR
1
2
3
4
5
6
7
8
9
LS+
I1
I2
I3
I4
I5
I6
I7
I8
Indicator
Status
Description
RUN
On (green)
The module has the correct operating voltage (24V DC).
Off
The module has no power.
ERR
On (red)
If the system is in Stop mode, one or more of the inputs or
outputs is faulty, or the module is faulty.
Use the RSLogix Guard PLUS! software to verify the location
of the fault. If the module is faulty, replace the module
immediately, or the safety-related operation of the
GuardPLC 2000 controller is not maintained.
Off
The module is operational.
- 1755-HSC GuardPLC Controller Systems 1755-IF8 GuardPLC Controller Systems 1755-IB24XOB16 GuardPLC Controller Systems 1755-A6 GuardPLC Controller Systems 1755-L1 GuardPLC Controller Systems 1754-L28BBB GuardPLC Controller Systems 1753-IB20XOB8 GuardPLC Controller Systems 1753-OB16 GuardPLC Controller Systems 1753-IB16 GuardPLC Controller Systems 1753-L32BBBP-8A GuardPLC Controller Systems 1753-L32BBBM-8A GuardPLC Controller Systems 1753-L28BBBP GuardPLC Controller Systems 1753-L28BBBM GuardPLC Controller Systems