Chapter 8 Wire and Configure the 1753-IB16XOB8 Module
Safety-related Digital
Outputs
The module has 8 digital output pairs, each with a positive- and
negative-switching output. The digital outputs are not electrically
isolated.
An output is in the safe state when it is de-energized. Therefore,
outputs are switched off when a fault that affects the safety control of
those outputs occurs.
If an overload occurs, the affected output is switched off. If the total
current exceeds 9 A, all eight outputs are switched off. When the
overload is eliminated, the outputs are activated again according to
their current software-driven state.
Configuration
The digital outputs can be configured three ways.
•
1-pole switch (no line monitoring)
•
2-pole switch (with or without line monitoring)
•
3-pole switch (2-pole with common reference)
63
LS+
Sensor supply for inputs 13…16
40 mA buffered/1 A unbuffered
64
LS+
Sensor supply for inputs 13…16
40 mA buffered/1 A unbuffered
65
13
Digital input 13
66
14
Digital input 14
67
15
Digital input 15
68
16
Digital input 16
69
L-
Reference pole
70
L-
Reference pole
71
Ground
Shield
72
Ground
Shield
Terminal Number
Designation
Function
- 1755-HSC GuardPLC Controller Systems 1755-IF8 GuardPLC Controller Systems 1755-IB24XOB16 GuardPLC Controller Systems 1755-A6 GuardPLC Controller Systems 1755-L1 GuardPLC Controller Systems 1754-L28BBB GuardPLC Controller Systems 1753-IB20XOB8 GuardPLC Controller Systems 1753-OB16 GuardPLC Controller Systems 1753-IB16 GuardPLC Controller Systems 1753-L32BBBP-8A GuardPLC Controller Systems 1753-L32BBBM-8A GuardPLC Controller Systems 1753-L28BBBP GuardPLC Controller Systems 1753-L28BBBM GuardPLC Controller Systems