Chapter 18 Introduction to EtherNet/IP Communication
RSLogix Guard PLUS! software creates an EtherNet/IP branch under
the Protocols folder where it adds the scanner and the adapter
assemblies.
Scanner defines the GuardPLC controller’s scanner I/O space, which
consists of two buffers: one to store input data and one to store
output data.
The controller’s adapter input assembly, [120]IN_120, contains data
that is produced by the GuardPLC controller. The controller’s adapter
output assembly, [121]OUT_121, contains the data that is consumed
by the GuardPLC controller.
View the Controller IP
Settings
You need to know the IP settings for the GuardPLC controller when
you configure a device to communicate with it over the EtherNet/IP
network.
To view and configure the IP settings for the GuardPLC controller,
follow these steps.
1. Expand the controller in the project tree.
2. Right-click COM and choose Properties.
- 1755-HSC GuardPLC Controller Systems 1755-IF8 GuardPLC Controller Systems 1755-IB24XOB16 GuardPLC Controller Systems 1755-A6 GuardPLC Controller Systems 1755-L1 GuardPLC Controller Systems 1754-L28BBB GuardPLC Controller Systems 1753-IB20XOB8 GuardPLC Controller Systems 1753-OB16 GuardPLC Controller Systems 1753-IB16 GuardPLC Controller Systems 1753-L32BBBP-8A GuardPLC Controller Systems 1753-L32BBBM-8A GuardPLC Controller Systems 1753-L28BBBP GuardPLC Controller Systems 1753-L28BBBM GuardPLC Controller Systems