Module Variables for GuardPLC 1600 and 1800 Controllers and
Distributed I/O

The GuardPLC 1600 and 1800 controllers and distributed I/O support
these module parameters.

DO[0y].State

(2)

Read

Error mask for counter outputs 1…4

0x01

Error in output channel

0x02

Output channel switched off due to overcurrent

0x04

Error during readback of the output channel

0x08

Faulty initialization after counter reset

DO[0x].Value

(2)

Write

Output value of counter outputs 1…4 (These 4 outputs cannot be driven by counter presets.
They are driven by user software only.)

0

Output de-energized

1

Output activated

(1) Ox = counter 01 or 02.
(2) 0y = outputs 01, 02, 03, or 04

I/O Data

Read/Write

Description

I/O Data

Read/Write

Description

Module.SRS

Read

Slot number (System.Rack.Slot)

Module.Type

Read

Module type

0x00A5

Digital input module (DI20) for GuardPLC 1600 controllers

Digital input module (DI20) for 1753-IB20XOB8

Digital input module (DI8) for 1753-IB8XOB8

0x00E2

Digital input module (DI16) for 1753-IB16XOB8

0x002D

Digital input module (DI16) for 1753-IB16

0x005A

Digital output module (DO16) for 1753-OB16

0x003C

Digital relay output module (DO8) 1753-OW8

0x00B4

Digital output module (DO8) for GuardPLC 1600/1800 controllers, and
1753-IB20XOB8

0x005B

Digital output module (DO8) for 1753-IB8XOB8

0x00C4

Digital output module (DO8) for 1753-IB16XOB8