High-speed Counters
The GuardPLC 1200 and 1800 controllers feature inputs for high-speed
counting up to a maximum of 100 kHz. These counters are 24-bit, and
are configurable for either 5V or 24V DC. The counters can be used as
a counter or as a decoder for 3-bit Gray Code inputs. As a counter,
input A is the counter input, input B is the counter direction input,
and input Z is used for a reset.
The counter inputs must be connected by using shielded, twisted-pair
cables for each measurement input. The shields must be connected at
both ends. The input lines should be no more than 500 m (1640 ft) in
length. All reference (L-, C-, or I- depending on the controller)
connections are interconnected on the module in the form of common
reference pole.
Cables are clipped to the shield contact plate when connecting
counter inputs. See the instructions for connecting shielded cabling to
the shield contact plate on page
.
IMPORTANT
D
Do not terminate unused high-speed counter inputs.
- 1755-HSC GuardPLC Controller Systems 1755-IF8 GuardPLC Controller Systems 1755-IB24XOB16 GuardPLC Controller Systems 1755-A6 GuardPLC Controller Systems 1755-L1 GuardPLC Controller Systems 1754-L28BBB GuardPLC Controller Systems 1753-IB20XOB8 GuardPLC Controller Systems 1753-OB16 GuardPLC Controller Systems 1753-IB16 GuardPLC Controller Systems 1753-L32BBBP-8A GuardPLC Controller Systems 1753-L32BBBM-8A GuardPLC Controller Systems 1753-L28BBBP GuardPLC Controller Systems 1753-L28BBBM GuardPLC Controller Systems