Rockwell Automation 1755-OF8 GuardPLC Controller Systems User Manual
Page 112
![background image](/manuals/579232/112/background.png)
112
Publication 1753-UM001C-EN-P - March 2010
Chapter 12 High-Speed Counters
To enable the Gray code decoder to work correctly, configure these
parameters in the routine.
Parameter
Setting
Cnt[0x].5/24V Mode
true for 24V
or
false for 5V
The adjusted level also applies to inputs B and Z.
You must configure this parameter with a constant.
Cnt[0x].Auto Advance Sense
this setting has no function on the gray code
(set to false)
Cnt[0x].Direction
this setting has no function on the gray code
(set to false)
Cnt[0x].Gray Code
true
Cnt[0x].Reset
this setting has no function on the gray code
(set to true)
This manual is related to the following products:
- 1755-HSC GuardPLC Controller Systems 1755-IF8 GuardPLC Controller Systems 1755-IB24XOB16 GuardPLC Controller Systems 1755-A6 GuardPLC Controller Systems 1755-L1 GuardPLC Controller Systems 1754-L28BBB GuardPLC Controller Systems 1753-IB20XOB8 GuardPLC Controller Systems 1753-OB16 GuardPLC Controller Systems 1753-IB16 GuardPLC Controller Systems 1753-L32BBBP-8A GuardPLC Controller Systems 1753-L32BBBM-8A GuardPLC Controller Systems 1753-L28BBBP GuardPLC Controller Systems 1753-L28BBBM GuardPLC Controller Systems