Add ethernet/ip protocol to your project – Rockwell Automation 1755-OF8 GuardPLC Controller Systems User Manual
Page 208
208
Publication 1753-UM001C-EN-P - March 2010
Chapter 18 Introduction to EtherNet/IP Communication
Add Ethernet/IP Protocol to Your Project
Next, you need to add the Ethernet/IP protocol to your project in
RSLogix Guard PLUS software. Follow these steps.
1. In the Hardware Management window of RSLogix Guard PLUS
software, right-click Protocols and choose Add Ethernet/IP.
By default, the software creates one input assembly (120) and
one output assembly (121). Input and output are referenced to
the scanner. Thus, an input assembly is used to send data from
the GuardPLC controller to the PanelView Plus terminal. An
output assembly is used to send data from the PanelView Plus
terminal out to the GuardPLC controller.
For simplicity, use separate assemblies for each of the four types
of data transfer, as shown above.
•
Reading integers from the GuardPLC controller
•
Reading BOOLs from the GuardPLC controller
•
Writing integers to the GuardPLC controller
•
Writing integers to the GuardPLC controller
2. To add an assembly, right-click Ethernet/IP, choose New and
then either input or output assembly.
- 1755-HSC GuardPLC Controller Systems 1755-IF8 GuardPLC Controller Systems 1755-IB24XOB16 GuardPLC Controller Systems 1755-A6 GuardPLC Controller Systems 1755-L1 GuardPLC Controller Systems 1754-L28BBB GuardPLC Controller Systems 1753-IB20XOB8 GuardPLC Controller Systems 1753-OB16 GuardPLC Controller Systems 1753-IB16 GuardPLC Controller Systems 1753-L32BBBP-8A GuardPLC Controller Systems 1753-L32BBBM-8A GuardPLC Controller Systems 1753-L28BBBP GuardPLC Controller Systems 1753-L28BBBM GuardPLC Controller Systems