Pulse Testing Chapter 11
Input Configuration for
Pulse Testing
Set up these signals by using the Outputs tab of the digital inputs
Signal Connections dialogbox in RSLogix Guard PLUS! software.
Name
Description
Type
Initial
Value
Notes
Number of Pulse Channels
Number of pulse outputs being used
USINT
1 to 8
1…4 for 1753-IB16
1…8 for GuardPLC 1600/2000 controllers
1…8 for 1753-IB20XOB8
1…2 for 1753-IB8XOB8 and 1753-IB16XOB8
Pulse Slot
Slot occupied by the module with the
pulsed outputs
UDINT —
2 for GuardPLC 1600 controllers
2 for 1753-IB20XOB8
1 for 1753-IB16
3 for 1753-IB8XOB8
3 for 1753-IB16XOB8
1…6 for GuardPLC 2000 controllers
(wherever 1755-IB24XOB16 is located)
Pulse Delay
Pulse delay is both the low pulse
width and pulse test duration.
UINT
400
(default)
Values in
μ
s from 5…2000.
Error Code
Error code for each switch
BYTE
N/A
for error code descriptions.
Value
Value for each switch
BOOL
DI[xx].PulseChannel
Indicates which pulse output is
sourcing the input channel
USINT
1 to 8
1…4 for 1753-IB16
1…8 for GuardPLC 1600/2000 controllers
1…8 for 1753-IB20XOB8
1…2 for 1753-IB8XOB8 and 1753-IB16XOB8
DO[xx].Value
Initialization value for the pulse
outputs
BOOL
TRUE
Each pulse output must be activated.
- 1755-HSC GuardPLC Controller Systems 1755-IF8 GuardPLC Controller Systems 1755-IB24XOB16 GuardPLC Controller Systems 1755-A6 GuardPLC Controller Systems 1755-L1 GuardPLC Controller Systems 1754-L28BBB GuardPLC Controller Systems 1753-IB20XOB8 GuardPLC Controller Systems 1753-OB16 GuardPLC Controller Systems 1753-IB16 GuardPLC Controller Systems 1753-L32BBBP-8A GuardPLC Controller Systems 1753-L32BBBM-8A GuardPLC Controller Systems 1753-L28BBBP GuardPLC Controller Systems 1753-L28BBBM GuardPLC Controller Systems