318
Publication 1753-UM001C-EN-P - March 2010
Appendix B System Signal Variables
Digital Output Module Variables for GuardPLC 1600/1800
Controllers, 1753-IB20XOB8 Modules, and 1753-OB16 Modules
The GuardPLC 1600 and GuardPLC 1800 controllers, 1753-IB20XOB8
modules, and 1753-OB16 modules support these digital output
parameters.
I/O Data
Read/Write
Description
DO.Error Code
Read
Error mask for all digital outputs
0x0001
Error in digital output range
0x0002
MEZ test of test pattern failed
0x0004
MEZ test, auxiliary supply failed
0x0010
FTZ test of test pattern failed
0x0020
FTZ test of test pattern of the output switch failed.
0x0040
FTZ test of the test pattern of the output switch (disconnection test
of outputs) failed.
DO[xx].Error Code
(1)
Read
Error mask of all digital output channels
0x01
Error in digital output module
0x02
Output switched off due to overload
0x04
Error when reading back the activation of the digital outputs
0x08
Error when reading back the status of the digital outputs
(1) xx = affected output channel of the controller or module.
- 1755-HSC GuardPLC Controller Systems 1755-IF8 GuardPLC Controller Systems 1755-IB24XOB16 GuardPLC Controller Systems 1755-A6 GuardPLC Controller Systems 1755-L1 GuardPLC Controller Systems 1754-L28BBB GuardPLC Controller Systems 1753-IB20XOB8 GuardPLC Controller Systems 1753-OB16 GuardPLC Controller Systems 1753-IB16 GuardPLC Controller Systems 1753-L32BBBP-8A GuardPLC Controller Systems 1753-L32BBBM-8A GuardPLC Controller Systems 1753-L28BBBP GuardPLC Controller Systems 1753-L28BBBM GuardPLC Controller Systems