Wire GuardPLC 1600, GuardPLC 1800, and
GuardPLC 1200 Controllers
Introduction
Power Supply Connections
Power supply connections for GuardPLC 1600, GuardPLC 1800, and
GuardPLC 1200 controllers are described in the following sections.
GuardPLC 1600 and GuardPLC 1800 Controllers
The supply voltage is connected via a 4-pin connector that
accommodates wire sizes up to 2.5 mm
2
(14 AWG). You only need to
connect one wire to L+ and one wire to L-. Both L+ and L- terminals
are internally connected. The other terminal can be used to
daisy-chain 24V DC to additional devices. The power supply
connector is rated to 10 A.
Topic
Page
Safety-related Digital Outputs
Wire the GuardPLC 1600 Controller
Wire the GuardPLC 1800 Controller
Wire the GuardPLC 1200 Controller
ATTENTION
Before connecting the power supply, check for correct polarity,
value, and ripple.
Do not reverse the L+ and L- terminals or damage to the
controller will result. There is no reverse polarity protection.
- 1755-HSC GuardPLC Controller Systems 1755-IF8 GuardPLC Controller Systems 1755-IB24XOB16 GuardPLC Controller Systems 1755-A6 GuardPLC Controller Systems 1755-L1 GuardPLC Controller Systems 1754-L28BBB GuardPLC Controller Systems 1753-IB20XOB8 GuardPLC Controller Systems 1753-OB16 GuardPLC Controller Systems 1753-IB16 GuardPLC Controller Systems 1753-L32BBBP-8A GuardPLC Controller Systems 1753-L32BBBM-8A GuardPLC Controller Systems 1753-L28BBBP GuardPLC Controller Systems 1753-L28BBBM GuardPLC Controller Systems