Configure connections in rsnetworx for ethernet/ip, Software – Rockwell Automation 1755-OF8 GuardPLC Controller Systems User Manual
Page 254
254
Publication 1753-UM001C-EN-P - March 2010
Chapter 20 Use the GuardPLC Controller as a Scanner
Configure Connections in
RSNetWorx for EtherNet/IP
Software
Before starting RSNetWorx for EtherNet/IP software and configuring
the GuardPLC controller’s scanlist, make sure the GuardPLC controller
is in the STOP/VALID CONFIGURATION state, or RSNetWorx for
EtherNet/IP software will generate an error.
1. Start RSNetWorx for EtherNet/IP software.
2. To create a new configuration, from the File menu, choose New.
3. To go online, click the online button or, from the Network
menu, choose Online.
Your EtherNet/IP devices appear in the graphic view.
TIP
You may see icons overlaying the devices when you first
go online. This is normal and only indicates the status of
the offline versus the online configuration. Once you
complete the configuration, the symbols disappear.
- 1755-HSC GuardPLC Controller Systems 1755-IF8 GuardPLC Controller Systems 1755-IB24XOB16 GuardPLC Controller Systems 1755-A6 GuardPLC Controller Systems 1755-L1 GuardPLC Controller Systems 1754-L28BBB GuardPLC Controller Systems 1753-IB20XOB8 GuardPLC Controller Systems 1753-OB16 GuardPLC Controller Systems 1753-IB16 GuardPLC Controller Systems 1753-L32BBBP-8A GuardPLC Controller Systems 1753-L32BBBM-8A GuardPLC Controller Systems 1753-L28BBBP GuardPLC Controller Systems 1753-L28BBBM GuardPLC Controller Systems