289

Specifications Appendix A

Digital Inputs

Number of inputs

16 (not electrically isolated)

1 Signal

Voltage: 15V … 30V DC, Current consumption:

2 mA @ 15V

0 Signal

Voltage, max: 5V DC
Current consumption, max: 1.5 mA (1 mA @ 5V)

Switching point

typically 7.5V

Switching time

typically 250

μ

s

Sensor supply

4 x 19.2V / 40 mA @ 24V short-circuit proof

Pulse Test Sources

Number of pulse test
sources

4 (not electrically isolated)

Output voltage range

approximately 24V

Output current

60 mA

Current load, min

none

Response to overload

4 x

19.2V, short circuit current 60 mA @ 24V

Environmental Conditions

Temperature, operating 0…60 °C (32…140 °F)

Temperature, storage

-40…85 °C (-40…185 °F)

Mechanical Dimensions

Width

152 mm (5.99 in.) including housing screws

Height

114 mm (4.49 in.) including latch

Depth

66 mm (2.60 in.) including grounding bolt

Weight

0.7 kg (1.54 lb)

Certifications (when product is marked)

c-UL-us

UL Listed Industrial Control Equipment, certified for US and
Canada

CE

European Union 89/336/EEC EMC Directive, compliant with:

EN 61000-6-4; Industrial Emissions

EN 50082-2; Industrial Immunity

EN 61326; Meas./Control/Lab., Industrial Requirements

EN 61000-6-2; Industrial Immunity

EN61131-2; Programmable Controllers (Clause 8, Zone A,
B, & C)

C-Tick

Australian Radiocommunications Act, compliant with:
AS/NZS CISPR 11; Industrial Emissions

Functional Safety

Certified by TÜV

Attribute

1753-IB16