Guardplc 1200 controller status indicators – Rockwell Automation 1755-OF8 GuardPLC Controller Systems User Manual
Page 142
142
Publication 1753-UM001C-EN-P - March 2010
Chapter 15 Diagnostics
GuardPLC 1200 Controller
Status Indicators
The GuardPLC 1200 controller has these status indicators.
PLC
1200
Indicator
State
Description
INput
On
Digital input channels are high (10 … 30V DC).
Off
Digital input channels are off.
OUTput
On
Digital output channels are high.
Off
Digital output channels are off.
RUN
On
This is the normal status of the controller.
A routine, which has been loaded into the controller, is executed. The controller processes input
and output signals, carries out communication, and performs hardware and software tests.
Flashing
The controller is in Stop mode and is not executing a routine.
All system outputs are reset.
Stop mode can be triggered by setting the system variable AB-CPU/Emergency Stop to TRUE in
the routine, or by direct command from the programming terminal.
Off
The controller is in Failure_Stop (see ERROR).
ERROR
On
•
A hardware error has been detected by the controller. In this case the controller goes to
Failure_Stop and the execution of the routine is halted. Hardware errors are errors in the
controller, in one or more of the digital input and output modules, or in the counters.
•
A software error in the operating system has been detected by the controller.
•
The watchdog has reported an error because of exceeded cycle time.
All system outputs will be reset and the controller ceases all hardware and software tests. The
controller can only be restarted by a command from the programming terminal.
Flashing
If all the status indicators are on and ERROR blinks, the boot loader detected a corrupted
operating system and is waiting for an operating system download.
Off
No errors are detected.
PROGress
On
The upload of a new controller configuration is in progress.
Flashing
The upload of a new operating system into the Flash ROM is in progress.
Off
No upload of controller configuration or operating system is in progress.
FORCE
On
The controller is executing a routine (Run) and Force mode is activated by the user.
Flashing
The controller is in Stop mode, but forcing has been saved and will be activated when the
controller is started.
Off
Forcing is off.
- 1755-HSC GuardPLC Controller Systems 1755-IF8 GuardPLC Controller Systems 1755-IB24XOB16 GuardPLC Controller Systems 1755-A6 GuardPLC Controller Systems 1755-L1 GuardPLC Controller Systems 1754-L28BBB GuardPLC Controller Systems 1753-IB20XOB8 GuardPLC Controller Systems 1753-OB16 GuardPLC Controller Systems 1753-IB16 GuardPLC Controller Systems 1753-L32BBBP-8A GuardPLC Controller Systems 1753-L32BBBM-8A GuardPLC Controller Systems 1753-L28BBBP GuardPLC Controller Systems 1753-L28BBBM GuardPLC Controller Systems