Appendix B System Signal Variables
DO.State
(1)
Read
Error mask for all digital outputs
0x0000
No errors detected
0x0001
Error of the DO section of the module
0x0002
Within the multiple error occurrence time: safety switch 1 faulty
0x0004
Within the multiple error occurrence time: safety switch 2 faulty
0x0008
Within the multiple error occurrence time: test sample tests faulty
0x0010
Within the multiple error occurrence time: readback channels faulty
0x0020
Within the multiple error occurrence time: active switch-off faulty
0x0100
Within the safety time: CS signals faulty
0x0200
All outputs switched off; total current too high
0x0400
Within the safety time: temperature limit 1 exceeded
0x0800
Within the safety: temperature limit 2 exceeded
0x01000
Within the safety time: auxiliary voltage monitoring: undervoltage
0x02000
Within the multiple error occurrence time: status of the
safety switches
DO[0x].State
(1)(2)
Read
Error mask for digital output channels
0x00
No error detected; outputs driven as expected
0x01
Error in digital output module; outputs not driven
0x02
Output switched off due to overcurrent; outputs not driven
0x04
Error during readback of the digital output; outputs not driven
DO[0x].Value
(1)
Write
Output value of digital output channels
0
Output de-energized
1
Output activated
DI.State
Write
Error mask for all digital inputs
0x0000
No error detected
0x0001
Error of the DI section of the module
0x0002
Within the safety time: test sample test faulty
DI[xy].State
(3)
Read
Error mask of digital input channels
0x00
No error detected
0x01
Error in the digital input module; input value set to 0
DI[xy].Value
(2)
Read
Input values of digital input channels
0
Input not activated
1
Input activated
(1) Values are ORed.
(2) 0x = output channel 01…16 for GuardPLC 2000 controller and 01…08 for GuardPLC 1200, 1600, and 1800 controllers.
(3) xy = input channel 01…24 for GuardPLC 2000 and GuardPLC 1800 controllers and 01… 20 for GuardPLC 1200 and 1600 controllers.
I/O Data
Read/Write
Description
- 1755-HSC GuardPLC Controller Systems 1755-IF8 GuardPLC Controller Systems 1755-IB24XOB16 GuardPLC Controller Systems 1755-A6 GuardPLC Controller Systems 1755-L1 GuardPLC Controller Systems 1754-L28BBB GuardPLC Controller Systems 1753-IB20XOB8 GuardPLC Controller Systems 1753-OB16 GuardPLC Controller Systems 1753-IB16 GuardPLC Controller Systems 1753-L32BBBP-8A GuardPLC Controller Systems 1753-L32BBBM-8A GuardPLC Controller Systems 1753-L28BBBP GuardPLC Controller Systems 1753-L28BBBM GuardPLC Controller Systems