Diagnostics Chapter 15
GuardPLC 2000 Controller
Status Indicators
The GuardPLC 2000 controller has status indicators for:
•
module, both the program and the communication.
•
controller and the system hardware.
•
routine.
•
Ethernet communication to the programming terminal.
Controller Indicators
Indicator Status
Description
RUN
On
This is the normal status of the controller (Run or Stop mode).
The controller carries out communication and performs software
tests.
Flashing
Downloading an Operating System
Off
The controller is in Failure_Stop (see ERR below), or there is no
power supply.
ERR
On
The controller is in the Failure_Stop state and the execution of
the routine is halted. All system outputs will be reset and the
controller ceases all hardware and software tests.
The operating system loader has found a flash error (FAULT is
blinking).
Flashing
The boot loader has found an error in the operating system in the
flash (if all other indicators are ON); the download of a new
operating system is awaited.
Off
No errors are detected.
10/100BaseT
Tx COL
FORCE
PROG FAULT
RUN STOP
RUN ERR
1755-
L1
- 1755-HSC GuardPLC Controller Systems 1755-IF8 GuardPLC Controller Systems 1755-IB24XOB16 GuardPLC Controller Systems 1755-A6 GuardPLC Controller Systems 1755-L1 GuardPLC Controller Systems 1754-L28BBB GuardPLC Controller Systems 1753-IB20XOB8 GuardPLC Controller Systems 1753-OB16 GuardPLC Controller Systems 1753-IB16 GuardPLC Controller Systems 1753-L32BBBP-8A GuardPLC Controller Systems 1753-L32BBBM-8A GuardPLC Controller Systems 1753-L28BBBP GuardPLC Controller Systems 1753-L28BBBM GuardPLC Controller Systems